mobile, or smaller homes, for example – it is
recommended a smoke alarm be placed as far
from these fuel-burning sources as possible.
The placement recommendations are intended
to keep a smoke detector at a reasonable
distance from a fuel-burning source, reducing
“unwanted” alarms. Unwanted alarms can
occur if a smoke alarm is placed directly next
to a fuel-burning source. Ventilate these areas
as much as possible.
In air streams near kitchens. Air currents
can draw cooking smoke into the sensor of a
smoke alarm near the kitchen.
In very damp, humid or steamy areas, or
directly near bathrooms with showers. Keep
a smoke alarm at least 3 metres (10 feet) away
from showers, saunas, dishwashers, etc.
Where temperatures are regularly below
4 °C (40 °F) or above 38 °C (100 ° F) including
unheated buildings, outdoor rooms, porches,
or unfinished attics or cellars.
In very dusty, dirty, or greasy areas. Do not
install a smoke alarm directly over the stove or
range. Clean a laundry room unit frequently to
keep it free of dust or lint.
Near fresh air vents, ceiling fans, or in very
drafty areas. Drafts can blow smoke away
from a smoke alarm, preventing it from
reaching the sensor.
In insect infested areas. Insects can
clog openings to the sensor and cause
unwanted alarms.
Less than 30.48 cm (12 inches) away from
fluorescent lights. Electrical “noise can
interfere with the sensor.
In “dead air” spaces. “Dead air” spaces may
prevent smoke from reaching a smoke alarm.
SMOKE DETECTION
Are more smoke alarms desirable?
The required number of smoke alarms might
not provide reliable early warning protection
for those areas separated by a door from the
areas protected by the required smoke alarms.
For this reason, the use of additional smoke
alarms for those areas is recommended for
increased protection. The additional areas
include the dining room and hallways not
protected by the required smoke alarms.
The installation of smoke alarms in kitchens,
attics (finished or unfinished), or garages is
not normally recommended, because these
locations occasionally experience conditions
that can result in improper operation. As Nest
Protect is also a carbon monoxide alarm, it is
not recommended to install it in a furnace room
or a utility room if it contains a water heater or
a boiler. It should be outside a utility room or at
least 5 – 6 m (15 – 20 ft) from these appliances
to avoid transient conditions and/or perceived
nuisance alarms.
WHERE NOT TO INSTALL YOUR SMOKE ALARMS
For best performance, AVOID installing a smoke
alarm in these areas:
Where combustion particles are produced.
Burning material creates combustion particles
which could cause your smoke alarm to go off
unnecessarily. Areas to avoid include poorly
ventilated kitchens, garages, boats, recreational
vehicles and boiler rooms. Keep a smoke alarm
at least 6 metres (20 feet) from from the source
of combustion particles (stove, furnace, water
heater, space heater) if possible. In areas where
a 6 metres (20-foot) distance is not possible – in
21
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nest Protect Battery at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nest Protect Battery in the language / languages: English as an attachment in your email.

The manual is 1,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Nest Protect Battery

Nest Protect Battery User Manual - Dutch - 31 pages

Nest Protect Battery User Manual - French - 35 pages

Nest Protect Battery User Manual - French - 33 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info