TECHNICAL MANUAL TS 3x.10 KNX ENGLISH
32
Designation
Options
Description
Differentiation
between short and
long actuation
Inactive
No differentiation between short and long actuation of input. Thereby:
Opening the contact leads to event 0.
Closing the contact leads to
event 1.
Activate minimum signal
duration
Inactive
Active
Function disabled.
Minimum signal duration for open / close configurable (see the following parameter).
At contact opening
in value x 0,1s
1…65535
x 0,1 seconds
Parameter for minimum signal duration of open contact.
At contact closing
in value x 0,1s
1…65535
x 0,1 seconds
Parameter for minimum signal duration of „close contact“.
Query input after download,
ETS reset and bus voltage
recovery
Inactive
Active
Function disabled.
Configurable waiting time before transmission after a restart. (0…30000 seconds)
Active
Differentiation between short and long actuation of input active. Thereby:
Short actuation event 0;
Long actuation
event 1
Long actuation from …s
0,3 to 10,0 seconds
If active, definition of when to count the actuation as a „long actuation“ can be done.
Input is being actuated
Closed
Opened
Definition of function of input either as NO or NC contact.
Reaction in case of
event 0 / 1
Inactive
Switch
Priority
1-Byte value
Scene
2-Byte value
2-Byte floating point
4-Byte value
If inactive function disabled.
Selection of the desired data / transmission type.
Sent value
Selection depending on
configuration of
parameter “reaction in
case of event 0/1
Debouncing time
10 to 150 ms
Definition of debouncing time for the input.
Enable object
„disable“
Inactive
Active
Communication object (blocking object) for input is disabled.
Communication object (blocking object) for input is enabled.
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Muller TS 30.10 knx at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Muller TS 30.10 knx in the language / languages: English as an attachment in your email.

The manual is 1,69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Muller TS 30.10 knx

Muller TS 30.10 knx User Manual - English - 2 pages

Muller TS 30.10 knx Installation Guide - German - 46 pages

Muller TS 30.10 knx User Manual - German - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info