section 5 - installation instructions
5.7 DETERMINING THE FLUE LENGTH
IMPORTANT. The boiler must be installed in a vertical position in accordance to the installation instructions.
STANDARD FLUE KITS
-contains:Flueturret,nontelescopicsinglepieceueincorporatingaterminal
and inner rubber wall seal.
Extension Kit RSF341 -contains:1metrelengthofuepipe(Functionallength950mm),1supportbracket.
When extension kits are used the ue duct must incline 1.5 degrees away from the appliance, to allow the condensate to drain back to
the boiler and out of the condensate drain. It is recommended that a support bracket is tted on every 1 metre of pipe work used and the
bracket is located as close to the collar as possible. The bracketing must ensure a 1.5 degree fall back to the appliance.
Only use water as a lubricant during assembly.
Thehorizontaluekitterminalisclassedaspartofthemaximumuelength.


create an adequate seal.
ItisIMPORTANTthatallattachmentsarettedinaccordancewiththeinstallationinstructionsprovidedinthismanual.
TheTURRETsuppliedintheHorizontalFlueKits(RSF303&RSF305)hasanuppercombustionsamplepointwithascrewcapseal
andalowerairsamplepointwithanairstopperseal.Ensureallcaps&sealsareinplace.
Additional Termination KitsavailableforusewiththeseHorizontalFlueKits(RSF303&RSF305)
FlueDeectorKit(RSF300) Theresistanceistheequivalentof1metreofuepipeandthereforemustbedeductedfrom
anymaximumuelength
Total Maximum Permissible Horizontal Concentric Flue Length combining both Horizontal Flue Kits and Extension Kits
(Measuredfromcentrelineoftheturrettotheoutsidefaceofthealuminiumuecollar(RSF060))
24 kW appliances TotalMaximum:8metres-minusanyuekitoptions
30 kW Appliances TotalMaximum:7metres-minusanyuekitoptions
Total Maximum Permissible Vertical Flue Length
24&30kWAppliances Total Maximum: 7.5 Metres - minus any 90º bends
Minimum Horizontal Flue Lengths (Centrelineofturrettooutsidefaceofthealuminiumuecollar(RSF060))
Rear Flue - 191mm
Side Flue - 236mm (with minimum 2.5mm clearance)
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Morco GB30 SII at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Morco GB30 SII in the language / languages: English as an attachment in your email.

The manual is 6,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Morco GB30 SII

Morco GB30 SII User Manual - Dutch - 10 pages

Morco GB30 SII User Manual - French - 10 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info