60
-
'13 • SRK-T-144
• Models SRK50, 60
(i) Operating conditions:
When the outdoor air temperature (TH2) is lower than 4ºC or higher continues for 30 sec-
onds while the compressor command speed is other than 0 rps.
(ii)
Detail of operation:
The lower limit compressor command speed is change as shown in the gure below.
(iii)
Reset conditions:
When either of the following condition is satised.
1)
The outdoor air temperature (TH2) becomes 6ºC.
2)
The compressor command speed is 0 rps.
-8 -6
Lower limit 45 rps
Lower limit 35 rps
Normal operation
4 6
Outdoor air temperature C)
(i) Compressor overheat protection
(i) Purpose:
It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the
compressor overheat.
(ii)
Detail of operation
1) Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe.
Discharge pipe temperature (˚C)
Lower limit
(4)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
After lapse of 3 min. or over
(3)
4 rps
4 rps
(1)
0 rps
(Example) Fuzzy
90 (95) 100 (105) 110 (115)
Notes
(1) When the discharge pipe temperature is in the range of 100~110
ºC (105~115ºC), the speed is reduced by 4 rps.
(2)
When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4 rps.
(3) If the discharge pipe temperature is in the range of 90~100ºC (95~105ºC) even when the compressor command speed is maintained for 3 min-
utes when the temperature is in the range of 90~100ºC (95~105ºC), the speed is raised by 1 rps and kept at that speed for 3 minutes. This
process is repeated until the command speed is reached.
(4)
Lower limit speed
2) If the temperature of 110ºC (115ºC) is detected by the sensor on the discharge pipe, then the compressor will stop
immediately.
When
the discharge pipe temperature drops and the time delay of 3 minutes is over, the unit starts again within 1
hour but there is no start at the third time.
(j)
Current safe
(i) Purpose:
Current is controlled not to exceed the upper limit of the setting operation current.
(ii)
Detail of operation:
Input current to the converter is monitored with the current sensor xed on the printed circuit
board of the outdoor unit and, if the operation current value reaches the limiting current value, the
compressor command speed is reduced.
If the mechanism is actuated when the compressor command speed is less than 30 rps, the com-
pressor is stopped immediately. Operation starts again after a delay time of 3 minutes.
Cooling Heating
Lower Limit Speed
SRK20~35
20 rps 30 rps
SRK50, 60
25 rps 32 rps
Item
Model
(5)
Value in ( ) are for the model SRK50, 60.
61


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mitsubishi SRK35ZMX-S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mitsubishi SRK35ZMX-S in the language / languages: English as an attachment in your email.

The manual is 21,74 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Mitsubishi SRK35ZMX-S

Mitsubishi SRK35ZMX-S User Manual - English - 34 pages

Mitsubishi SRK35ZMX-S User Manual - German - 34 pages

Mitsubishi SRK35ZMX-S User Manual - Dutch - 34 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info