664856
141
Zoom out
Zoom in
Previous page
1/144
Next page
-
138
-
8.3.6 Refrigerant recharging at servicing
When it becomes necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following
steps.
(For details, see the instruction manual prepared by the equipment manufacturer)
1) Connect the charge hose to the outdoor unit’s service port.
2) Connect the charge hose to the vacuum pump adapter. At this time, keep the control valves in the fully opened position.
3) Place the handle Lo in the fully opened position, and turn ON the vacuum pump’s power source. (For the evacuating time, refer
to the equipment manufacturer’s manual)
4) When the compound gauge’s pointer has indicated -0.1 MPa (-76 cmHg), place the handle Lo in the fully closed position, and
turn OFF the vacuum pump’s power source. Keep this state for 1 ~ 2 minutes, and ascertain that the compound gauge’s pointer
does not return.
5) Charge liquid refrigerant by using the electronic balance according to the steps described in Section 8.3.2 (2) (pages136, 137).
8.4 Refrigerant recovery
8.4.1 Recovering procedures
The following procedures for refrigerant recovery represent general procedures, and they may differ between actual cases depend-
ing upon the type of refrigerant recovering equipment. The connecting and handling methods for different type of refrigerant
recovering equipment may also differ. So, ascertain the details by referring to the respective instruction manuals, etc.
(1) Checks prior to recovering procedures
a) Checking the refrigerant recovering equipment
1 Gas leakage [If there is any malfunction, repair it].
2 Oil separator [Drain the residual oil].
3 Recovering equipment weighing function, overcharge preventing function (float switch), moisture indicator, drier and
other accessory functions [should be adjusted or replaced where necessary].
4 Electrical circuit
b) Checking the accessories to the refrigerant recovering equipment
(2) Preparations for recovering procedures
a) Installation of refrigerant recovering equipment
Install the equipment in a place which satisfies the following requirements as much as possible.
1 Ambient temperature is higher than 0°C and lower than 40°C.
2 A flat and dry floor.
3 A place as close to the air conditioner as possible.
b) Preparation of recovering cylinder
A recovering cylinder should be such that it does not go against prohibitions, and is suitable for refrigerant recovered.
c) Connect to the power source
d) Preparations for air conditioner subjected to refrigerant recovery
1 When it is possible to run the air conditioner subjected to refrigerant recovery, perform pump down operation so that
refrigerant is contained in the outdoor unit (condenser side).
Carry out the pump down operation after confirming the specification of the air conditioner subjected to refrigerant
recovery.
2 If there is any clogging part (ex. the electronic expansion valve, etc.), fully open such part.
(3) Connection of refrigerant recovering equipment
a) Connect the air conditioner subjected to refrigerant recovery to the refrigerant recovering equipment.
1 When there is a service port (port for recovery):
Make connection to the service port (port for recovery) by using a gauge manifold and charge hose.
2 When there is no service port (port for recovery):
Make connection in a manner similar to 1 above by using a piercing valve.
b) Connect the refrigerant recovering equipment to the recovering cylinder.
Recovering cylinder
Gauge manifold
(Intake
port)
(Discharge
port)
Refrigerant
recovering
equipment
Air conditioner
subjected to
recovery
141


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mitsubishi SKM25ZG-S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mitsubishi SKM25ZG-S in the language / languages: English as an attachment in your email.

The manual is 6,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Mitsubishi SKM25ZG-S

Mitsubishi SKM25ZG-S User Manual - German - 24 pages

Mitsubishi SKM25ZG-S User Manual - Dutch - 24 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info