664854
130
Zoom out
Zoom in
Previous page
1/144
Next page
-
127
-
(3) Lubricating oils for R410A
As the lubricating oils for R22, mineral oils, alkylbenze synthetic oils, etc. have so far been used. As R410A features less solubility
with these conventional lubricating oils such as mineral oils, the lubricating oils tend to stay within the refrigeration cycle. As the
lubricating oils highly soluble with R410A, ester, ethereal and other synthetic oils are available. However, as these synthetic oils
are very hygroscopic, they must be treated even more carefully than the conventional lubricating oils. Furthermore, if these syn-
thetic oils are mixed with mineral oils, alkylbenzene synthetic oils, etc., they may deteriorate, and block the capillary tubes, or
cause the compressor to fail. So, never mix these synthetic oils.
8.1.2 Safety during installation/servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By
using tools and materials exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following
precautions into consideration.
1) Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
2) If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
3) When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise,
pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
4) After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan driven heater, space heater, etc., a poisonous
gas may occur.
5) When an air conditioning system charged with a large volume of refrigerant (e.g.multi type air conditioner) is installed in a
small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal
level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
6) Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
7) Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air condi-
tioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
8.2 Refrigerant piping installation
8.2.1 Piping materials and joints used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant
must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less
affected by contaminants.
(1) Copper pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of
residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the
interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3. Never use copper pipes thinner than 0.8 mm even when it
is available on the market.
Thickness (mm)
Nominal
Outer diameter
R410A [ref.] R22
diameter (mm)
1/4 6.35 0.80 0.80
3/8 9.52 0.80 0.80
1/2 12.70 0.80 0.80
5/8 15.88 1.00 1.00
Table 3. Thicknesses of annealed copper pipes
130


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mitsubishi SKM20ZG-S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mitsubishi SKM20ZG-S in the language / languages: English as an attachment in your email.

The manual is 6,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Mitsubishi SKM20ZG-S

Mitsubishi SKM20ZG-S User Manual - German - 24 pages

Mitsubishi SKM20ZG-S User Manual - Dutch - 24 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info