LED1(Red) LED2(Yellow)
Lightning Twice Outdoor power system
• Check the connection of the compressor connecting
wire.
• Refer to 10-6.A "How to check inverter/compressor".
• Check the stop valve.
Lightning 3 times Discharge temperature
thermistor • Refer to 10-6.B "Check of outdoor thirmistors".
• Refer to 10-6.B "Check of outdoor thirmistors".
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lightning 7 times Nonvolatile memory data • Replace the outdoor electronic control P.C. board.
Lightning 8 times Current sensor • Replace the power board.
Lightning 11 times Communication error
between P.C. boards • Check the connecting wire between outdoor electronic control
P.C. board and power board.
Lightning 12 times Zero cross detecting
circuit • Check the connecting wire among outdoor electronic control
P.C. board, noise filter P.C. board and power board.
Abnormal point / Condition Correspondence
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 5 minutes (in
cooling) and 10 minutes (in heating) of compressor start-up.
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 5 minutes of
compressor start-up.
• Refer to 10-6.B "Check of outdoor thirmistors".
• Replace the outdoor electronic control P.C. board.
Indication
When over current protection stop is continuously
performed three times within 1 minute after the compressor gets
started, or when converter protection stop or bus-bar voltage
protection stop is continuously performed three times within 3
minutes after start-up.
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 10 minutes
of compressor start-up.
Condition
When the nonvolatile memory data cannot be read properly.
Lightning 6 times Serial signal
Fin temperature
thermistor
P.C board temperature
thermistor
Lightning 4 times
Ambient temperature
thermistor
Current sensor protection stop is continuously performed twice.
When the communication protection stop between boards is
continuously performed twice.
The protection stop of the zero cross detecting circuit is continuously
performed 10 times.
When a short or open circuit is detected in the thermistor during
operation.
When a short or open circuit is detected in the thermistor during
operation.
5 timesLightning
Outdoor electronic control P.C. board(Parts side)
Lighting
IPM protection
Lock protection
3 times Goes out Discharge temperature
protection • Check the amount of gas and refrigerant circuit.
• Refer to 10-6.G "Check of LEV".
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
8 times Goes out Converter protection • Replace the power board.
Bus-bar voltage
protection (1) • Replace the power board.
Bus-bar voltage
protection (2)
13 times Goes out Outdoor fan motor • Refer to 10-6.D "Check of outdoor fan motor".
Lighting 8 times Current sensor
protection • Replace the power board.
Lighting 11 times
Communication between P.C.
boards protection
• Check the connecting wire between outdoor electronic control
P.C. board and power board.
Lighting 12 times Zero cross detecting circuit
protection • Check the connecting wire among outdoor electronic control
P.C. board, noise filter P.C. board and power board.
•Check refrigerant circuit and refrigerant amount.
•Refer to 10-6.D "Check of outdoor fan motor".
• Check around of gas and the refrigerant circuit.
• Check of stop valve.
• Reconnect compressor connector.
• Refer to 10-6.A "How to check inverter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice Goes out
4 times Goes out
5 times Goes out
9 times Goes out
When over-current is detected after 30 minutes of compressor start-up.
When over-current is detected within 30 minutes of compressor
start-up
When the bus-bar voltage exceeds 400V or falls to 200V or below
during compressor operating.
When the bus-bar voltage exceeds 400V or falls to 50V or below
during compressor operating.
When discharge temperature exceeds 116:during operation.
compressor stops. Compressor can restart if discharge temperature
thermistor reads 100: or less 3 minutes later.
When the fin temperature exceeds 87: during operation.
When the P.C. board temperature exceeds 70: during operation.
When failure occurs continuously three times within 30 seconds after
the fan gets started.
When a short or open circuit is detected in the current sensor during
compressor operating.
Communication error occurs between the outdoor electronic control P.C.
board and power board for more than 10 seconds.
When zero cross signal cannot be detected while the compressor is
operating.
When the outdoor heat exchanger temperature exceeds 70:
during cooling or when indoor gas pipe temperature exceeds 70:
during heating.
When a failure is detected in the operation of the converter during
operation.
Outdoor unit
does not
operate.
LED2 LED1
Refer to 10-6.H "How to check mis-wiring and serial signal
error.
When the communication fails between the indoor and outdoor
unit for 3 minutes.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit
stops and
restarts 3
minutes
later' is
repeated.
MUZ-GB50VA
ON
OFF 2.5-second OFF 2.5-second OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”. 0.5-second ON 0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure. Refer to 10-7.1.
2. LED is lighted during normal operation.
10-4. Troubleshooting check table
OB455A--1qxq 06.7.31 2:19 PM Page 21
Downloaded from www.Manualslib.com manuals search engine
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mitsubishi MUZ-GB50VA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mitsubishi MUZ-GB50VA in the language / languages: English as an attachment in your email.

The manual is 3,64 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info