installation manual
CAUTION
Table 7-4
Ø6.35 Ø9.52 Ø12.7
15g/m×L
30g/m×L 60g/m×L
15g/m×(L-5)
30g/m×(L-5)
60g/m×(L-5)
Added Refrigerant
When Over
5m(One-way)
Less than 5m
(One-way)
R(g)
L(m)
D(mm)
R22
R22
R410A
R410A
Additional Refrigerant Charge
7.2
Refrigerant cannot be charged until field wiring has been
completed.
Refrigerant may only be charged after performing the leak
test and the vacuum pumping.
When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in view of
the danger of liquid hammer.
Charging with an unsuitable substance may cause explosions
and accidents, so always ensure that the appropriate
refrigerant is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when
charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate
the added refrigerant according to the diameter and the
length of the liquid side pipe of the outdoor unit/indoor unit
connection.
R(g): Additional refrigetant to be charged
L(m): The length of the refrigerant pipe(one-way)
D(mm)
: Liquid Side Piping Diameter
Fig.7-11
NOTE
Pressure meterMulti-meter
-76 cmHg
Lo-lever
Lo-lever
Charge hose Charge hose
Vacuum pump
Hi-lever
Manifold valve
If a negative result is gotten for R from the formule at
right, no refrigam needs to be added nor removed.
CAUTION
The drain pipe of indoor unit must be heat insulated, or it will
condense dew, as well as the connections of the indoor unit.
Hard PVC binder must be used for pipe connection, and make
sure there is no leakage.
With the connection part to the indoor unit, please be noted not
to impose pressure on the side of indoor unit pipes.
When the declivity of the drain pipe downwards is over 1/100,
there should not be any winding.
The total length of the drain pipe when pulled out traversely
shall not exceed 20m, when the pipe is over long, a prop stand
must be installed to prevent winding.
Refer to the figures on the right for the installation of the pipes.
8. CONNECT THE DRAIN PIPE
Install the drainpipe of the indoor unit
The outlet has PTI screw bread, Please use sealing materials
and pipe sheath(fitting) when connecting PVC pipes.
Drainage test
Check whether the drainpipe is unhindered.
New built house should have this test done before
paving the ceiling.
1.5m~2m
Insulating
material
Downward declivity
lower than 1/100
Bend
S shape
VP30
Downward declivity
lower than 1/100
Put as deep as possible
(about 10cm)
Fig. 8-1
Install the drain joint of the outdoor unit
Fit the seal into the drain joint, then insert the drain joint into the
base pan hole of outdoor, rotate 90 to securely assemble them.
Connect the drain joint with an extension drain hose (Locally
purchased), in case of the condensate draining off the outdoor
unit during the heating mode.(Refer to Fig.8-2)
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Midea MFAD-Serie at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Midea MFAD-Serie in the language / languages: English as an attachment in your email.

The manual is 2,83 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Midea MFAD-Serie

Midea MFAD-Serie User Manual - English - 12 pages

Midea MFAD-Serie Installation Guide - German - 16 pages

Midea MFAD-Serie User Manual - German - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info