10.5.5 Current protection
Model Current Compressor
I>12 A Off
10.5A<I<12A
Decrease frequency of compressor
Current up MSH-12HRDN1
I< 10.5A On
I>11.5 A Off
8.5A<I<11.5A
Decrease frequency of compressor
Current down MSH-09HRDN1
I< 8.5A On
11.5.6 Rated capacity test
Set mode to cooling mode
Set temp. to 17°C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test
Turbo function
Increasing frequency of compressor
After operating 30 minutes, return automatically to the mode and temp. previously selected.
10.6. Dehumidifying mode
10.6.1. The 4-way valve is off
10.6.2. the indoor fan is fixed in breeze speed
10.6.3. Compressor run in low frequency
10.6.4. Low room temperature protection:
When room temperature decreases to below 10 , compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 12 .
10.6.5. At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of
cooling mode.
10.7. Heating mode
10.7.1. Generally, the 4-way valve is open at heating mode, but it is closed at defrosting. 4-way valve must
delay 2 minutes compared with compressor if the compressor changed into non-heating mode or
turned off. 4-way valve doesn't delay in dehumidifying mode.
10.7.2. Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
10.7.3. Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3 Off Off Room temp. up
T<Ts+3 On On
T< Ts+2 On On Room temp. down
T>Ts+2 Off Off
10.7.4. Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Midea Alfa inverter 12 HRDN1 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Midea Alfa inverter 12 HRDN1 in the language / languages: English as an attachment in your email.

The manual is 0,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info