Air and moisture in the refrigerant system have undesirable effects as indicated below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested
and evacuated to remove any noncondensables and moisture from the system.
Air purging with vacuum pump
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units
have been properly connected and all wiring for the test run has been completed. Remove
the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both
the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Pipe length and refrigerant amount:
Connective pipe length
NOTE: N=2(one-twin models), N=3(one-three models), N=4(one-four models), N=5(one-five models).
The Standard pipe length is vary according to the requirements of different area. For example, in North
America area, the standard pipe length is 7.5m(25ft). While in the other areas, the standard pipe length is
5m(16ft).
Pre-charge pipe length(ft/m)
(Standard pipe lengthxN)
More than (Standard pipe lengthxN)ft/m
Air purging
method
Use vacuum
pump.
Use vacuum
pump.
Additional amount of refrigerant to be charged
(R410A)
AIR PURGING
Air purging
35
Liquid side: 6.35(1/4 )
(Total pipe length - standard pipe lengthxN)x15g(0.16oZ)/m(ft)
Liquid side: 9.52(3/8 )
(Total pipe length - standard pipe lengthxN)x30g(0.32oZ)/m(ft)
When relocate the unit to another place, perform evacuation using vacuum pump.
Make sure the refrigerant added into the air conditioner is liquid form in any case.
Open the valve stem until it hits against the
stopper. Do not try to open it further.
Securely tighten the valve stem cap with a
spanner or the like.
Valve stem cap tightening torque (See
Tightening torque table in previous page ).
Outdoor
unit
Indoor
unit
Refrigerant
Flare nut
Stopper
Cap
Valve body
Packed valve
Half union
Gas side
Liquid side
A
C
D
B
Valve stem
Fig.65
Fig.66
Caution in handling the packed valve
When Using the Vacuum Pump
(For method of using a manifold valve, refer
to its operation manual.)
1. Completely tighten the flare nuts, A, B, C, D,
connect the manifold valve charge hose to a
charge port of the low-pressure valve on the
gas pipe side.
2. Connect the charge hose connection to the
vacuum pump.
3. Fully open the handle Lo of the manifold valve.
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Midea 2M-53K at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Midea 2M-53K in the language / languages: English as an attachment in your email.

The manual is 10,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Midea 2M-53K

Midea 2M-53K User Manual - English - 33 pages

Midea 2M-53K Installation Guide - German - 39 pages

Midea 2M-53K User Manual - German - 33 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info