MI 3100 s, MI 3100 SE EurotestEASI Measurements
49
Note:
High fluctuations of mains voltage can influence the measurement results (the noise sign
is displayed in the message field). In this case it is recommended to repeat few
measurements to check if the readings are stable.
5.6.2 Voltage drop
The voltage drop is calculated based on the difference of line impedance at connection points
(sockets) and the line impedance at the reference point (usually the impedance at the
switchboard).
Circuits for measurement of voltage drop
Figure 5.30: Phase-neutral or phase-phase voltage drop measurement – connection of plug
commander and 3-wire test lead
Voltage drop measurement procedure
Step 1: Measuring the impedance Zref at origin
Select the Zline function using the function selector switch.
Set sub-function to U using UP / DOWN keys.
Select test parameters (optional).
Connect test cable to the instrument.
Connect the test leads to the origin of electrical installation (see Figure 5.30).
Press the CAL key to perform the measurement.
Step 2: Measuring the voltage drop
Set sub-function to U using UP / DOWN keys.
Select test parameters (Fuse type must be selected).
Connect test cable or plug commander to the instrument.
Connect the test leads to the tested points (see Figure 5.30).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (MI 3100 SE only).
49


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI3100S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI3100S in the language / languages: English as an attachment in your email.

The manual is 1.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI3100S

Metrel MI3100S User Manual - German - 92 pages

Metrel MI3100S User Manual - Dutch - 25 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info