MI 3100 s, MI 3100 SE EurotestEASI Measurements
36
R LOW measurement procedure
Select R LOW function using the function selector switch.
Set sub-function to R LOW using UP / DOWN keys.
Enable and set limit (optional).
Connect test cable to the instrument.
Compensate the test leads resistance (if necessary, see section 5.3.3 Compensation of
test leads resistance).
Disconnect from mains supply and discharge installation to be tested.
Connect the test leads to the appropriate PE wiring (see Figure 5.9).
Press the TEST key to perform the measurement.
After the measurement is finished store the result by pressing the MEM button (MI 3100
SE only).
Figure 5.10: Example of RLOW result
Displayed result:
R ............... R LOW resistance
R+ ............. result at positive polarity
R- .............. result at negative test polarity
5.3.2 Continuous resistance measurement with low current
In general, this function serves as standard -meter with a low testing current. The
measurement is performed continuously without polarity reversal. The function can also be
applied for testing continuity of inductive components.
Test circuit for continuous resistance measurement
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI3100S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI3100S in the language / languages: English as an attachment in your email.

The manual is 1.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI3100S

Metrel MI3100S User Manual - German - 92 pages

Metrel MI3100S User Manual - Dutch - 25 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info