776238
123
Zoom out
Zoom in
Previous page
1/204
Next page
MI 3152(H) EurotestXC (2,5 kV) Tests and measurements
122
7.13 Z line m – High precision line impedance and
prospective short-circuit current
Figure 7.45: Z line mΩ menu
Measurement parameters / limits
Fuse Type
Selection of fuse type [Off, gG, NV, B, C, D, K, Custom]
Fuse I
Rated current of selected fuse
Fuse t
Maximum breaking time of selected fuse
Test 1)
Test [-, L/N, L/L, L1/N, L2/N, L3/N, L1/L2, L1/L3, L2/L3]
Ia(Ipsc)
Minimum short circuit current for selected fuse or custom value
1) The measuring results (for phase neutral or phase phase line) are set according to
the setting. The parameter is meant for documentation.
Refer to Fuse tables guide for detailed information on fuse data.
Connection diagram
Figure 7.46: Phase-neutral or phase-phase high precision Line impedance measurement
Connection of A 1143
123


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3152 - EurotestXC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3152 - EurotestXC in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3152 - EurotestXC

Metrel MI 3152 - EurotestXC User Manual - German - 213 pages

Metrel MI 3152 - EurotestXC User Manual - Dutch - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info