MI 3152(H) EurotestXC (2,5 kV) Tests and measurements
113
7.10 Zs rcd – Fault loop impedance and prospective fault
current in system with RCD
Zs rcd measurement prevents trip-out of the RCD in systems with the RCD.
Figure 7.35: Zs rcd menu
Measurement parameters / limits
Measurement parameters / limits
Protection
Protection type [TN, TTrcd]
Fuse Type 1)
Selection of fuse type [Off, gG, NV, B, C, D, K, Custom]
Fuse I 1)
Rated current of selected fuse
Fuse t 1)
Maximum breaking time of selected fuse
Isc factor
Isc factor [0.20 ... 3.00]
Ia(Ipsc) 1)
Minimum fault current for selected fuse or custom value
I ∆N2)
Rated RCD residual current sensitivity [10 mA, 30 mA, 100 mA, 300 mA,
500 mA, 1000 mA]
RCD type2)
RCD type [AC, A, F, B4), B+4),F]
Selectivity2)
Characteristic [G, S]
Test
Selection of test [-, L-PE, L1-PE, L2. PE, L3-PE] 3)
I test
Test current [Standard, Low]
Limit Uc2)
Contact voltage limit [12 V, 25 V, 50 V] 2)
1) Parameter or limit is considered if Protection is set to TN
2) Parameter or limit is considered if Protection is set to TTrcd
3) With Plug test cable or Plug commander Zs rcd is measured in the same way regardless
of the setting. The parameter is meant for documentation.
4) Model MI 3152 only
Refer to Fuse tables guide for detailed information on fuse data.
114


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3152 - EurotestXC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3152 - EurotestXC in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3152 - EurotestXC

Metrel MI 3152 - EurotestXC User Manual - German - 213 pages

Metrel MI 3152 - EurotestXC User Manual - Dutch - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info