MI 3152(H) EurotestXC (2,5 kV) Tests and measurements
96
Figure 7.12: Connection of 2.5 kV test lead (UN = 2.5 kV)
Measurement procedure
Enter the Diagnostic test function.
Set test parameters / limits.
Disconnect tested installation from mains supply and discharge installation as required.
Connect test cable to the instrument.
Connect test leads to object under test (see Figure 7.11 and Figure 7.12).
Different test cable must be used for testing with nominal test voltage UN 1000 V and
UN= 2500 V. Also different test terminals are used.
The standard 3-wire test lead, Schuko test cable or Plug / Tip commanders can be used
for the insulation test with nominal test voltages ≤ 1000 V. For the 2500 V insulation test
the two wire 2.5 kV test lead should be used.
Start the measurement. Internal timer begins to increment. When internal timer reaches
1 min R60 and DAR factor are displayed and short beep is generated. Measurement
can be interrupted at any time.
When internal timer reaches 10 min also PI factor is displayed and measurement is
completed. Wait until object under test is fully discharged.
After the measurement is finished wait until tested item is fully discharged.
Save results (optional).
Figure 7.13: Examples of Diagnostic test result
Measurement results / sub-results
Riso
Insulation resistance
Um
Actual test voltage
R60
Resistance after 60 seconds
DAR
Dielectric absorption ratio
PI
Polarization index
97


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3152 - EurotestXC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3152 - EurotestXC in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3152 - EurotestXC

Metrel MI 3152 - EurotestXC User Manual - German - 213 pages

Metrel MI 3152 - EurotestXC User Manual - Dutch - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info