MI 3152(H) EurotestXC (2,5 kV) Instrument operation
39
U0 3)
½IN1)
IN
2IN
5IN
TN / IT
120 V
t > 800 ms
t 800 ms
t < 150 ms
t < 40 ms
230 V
t > 400 ms
t 400 ms
TT
120 V
t > 300 ms
t 300 ms
230 V
t > 200 ms
t 200 ms
Table 4.2: Trip-out times according to IEC/HD 60364-4-41
½IN1)
IN
2IN
5IN
General RCDs
(non-delayed)
t> 1999 ms
t< 300 ms
t< 150 ms
t< 40 ms
Selective RCDs
(time-delayed)
t> 1999 ms
130 ms < t< 500 ms
60 ms < t< 200 ms
50 ms < t< 150 ms
Table 4.3: Trip-out times according to BS 7671
RCD type
IN (mA)
½IN1)
IN
2IN
5IN
Note
t
t
t
t
I
10
> 999 ms
40 ms
40 ms
40 ms
Maximum break time
II
> 10 30
300 ms
150 ms
40 ms
III
> 30
300 ms
150 ms
40 ms
IV S
> 30
> 999 ms
500 ms
200 ms
150 ms
130 ms
60 ms
50 ms
Minimum non-actuating time
Table 4.4: Trip-out times according to AS/NZS 30172)
Standard
½IN
IN
2IN
5IN
EN 61008 / EN 61009
300 ms
300 ms
150 ms
40 ms
IEC 60364-4-41
1000 ms
1000 ms
150 ms
40 ms
BS 7671
2000 ms
300 ms
150 ms
40 ms
AS/NZS 3017 (I, II, III)
1000 ms
1000 ms
150 ms
40 ms
Table 4.5: Maximum test times related to selected test current for general (non-delayed)
RCD
Standard
½IN
IN
2IN
5IN
EN 61008 / EN 61009
500 ms
500 ms
200 ms
150 ms
IEC 60364-4-41
1000 ms
1000 ms
150 ms
40 ms
BS 7671
2000 ms
500 ms
200 ms
150 ms
AS/NZS 3017 (IV)
1000 ms
1000 ms
200 ms
150 ms
Table 4.6: Maximum test times related to selected test current for selective (time-delayed)
RCD
1) Minimum test period for current of ½IN, RCD shall not trip-out.
2) Test current and measurement accuracy correspond to AS/NZS 3017 requirements.
3) U0 is nominal ULPE voltage.
Note
Trip-out limit times for PRCD, PRCD-K and PRCD-S are equal to General (non-delayed)
RCDs.
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3152 - EurotestXC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3152 - EurotestXC in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3152 - EurotestXC

Metrel MI 3152 - EurotestXC User Manual - German - 213 pages

Metrel MI 3152 - EurotestXC User Manual - Dutch - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info