MI 3152(H) EurotestXC (2,5 kV) General description
10
Trip out time measurement for B and B+ type RCDs in AUTO function is made with sine-
wave test current, while trip-out current measurement is made with d.c. test current (MI
3152 only).
Z loop, Zs rcd
The specified accuracy of tested parameters is valid only if the mains voltage is stable
during the measurement.
The measurement accuracy and immunity against noise are higher if I test parameter in
Zsrcd is set to ‘Standard’.
Fault loop impedance (Z loop) measurements will trip an RCD.
The Zs rcd measurement does not normally trip an RCD. However if a leakage current
from L to PE already flows or if a very sensitive RCD is installed (for example EV type)
the RCD could trip. In this case setting parameter I test to ‘Low’ can help.
Z line, Voltage drop
In case of measurement of ZLine-Line with the instrument test leads PE and N connected together
the instrument will display a warning of dangerous PE voltage. The measurement will be
performed anyway.
Specified accuracy of tested parameters is valid only if mains voltage is stable during the
measurement.
If the reference impedance is not set the value of ZREF is considered as 0.00 Ω.
The highest value of Zref, measured at different settings of the Test or Phase
parameters is used for Voltage drop (ΔU) measurement in Voltage drop single test,
Zauto single test, auto tests and Auto Sequences®.
Measuring Zref without test voltage present (disconnected test leads) will reset Zref
value to initial value.
Power, Harmonics, Currents
Consider polarity of current clamp (arrow on test clamp should be oriented toward
connected load), otherwise result will be negative!
Illumination
A 1172 and A 1173 illumination probes are supported by the instrument.
Artificial light sources reach full power of operation after a period of time (see technical
data for light sources) and should be therefore switched on for this period of time before
the measurements are taken.
For accurate measurement make sure that the milk glass bulb is lit without any shadows
cast by hand, body or other unwanted objects.
Refer to the Illuminance handbook -for more information.
Rpe
The specified accuracy of tested parameters is valid only if the mains voltage is stable
during the measurement.
Measurement will trip an RCD if the parameter RCD is set to ‘No’.
The measurement does not normally trip an RCD if the parameter RCD is set to ‘Yes’.
However, the RCD can trip if a leakage current from L to PE already flows.
IMD
It is recommended to disconnect all appliances from the tested supply to receive regular
test results. Any connected appliance will influence the insulation resistance threshold
test.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3152 - EurotestXC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3152 - EurotestXC in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3152 - EurotestXC

Metrel MI 3152 - EurotestXC User Manual - German - 213 pages

Metrel MI 3152 - EurotestXC User Manual - Dutch - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info