MI 3121H Smartec 2,5 kV Insulation / Continuity Warnings and notes
7
Notes related to measurement functions:
General
If there is any irregular condition on input terminals then the selected measurement
can't be performed.
Insulation resistancecontinuity measurements shall be performed on de-
energized objects, i.e. voltage between test terminals should be lower than 10 V!
PASS / FAIL indication is enabled when limit is set to ON. Apply appropriate limit
value for evaluation of measurement results.
Insulation resistance
When measuring insulation resistance between installation conductors all loads
must be disconnected and all switches closed!
The instrument automatically discharge tested object after finished measurement.
Click the TEST key twice for continuous measurement.
It is recommended to use the GUARD connection when high insulation resistance
(>10G Ω) is measured. You need optional 2.5 kV 3-wire test lead.
The guard terminal is internal impedance (660 kΩ) protected.
The DAR and PI diagnostic is automatically calculated during insulation
measurements.
Continuity functions
Parallel resistance paths and interfering currents in measured circuit will influence
the test result!
If necessary compensate test lead resistance before performing continuity
measurement, see 5.2.3.
Measurement of resistance of wire wound components like transformer or motor
windings is possible only in continuous function due to great influence of the
winding inductance.
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3121H SMARTEC 2.5 kV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3121H SMARTEC 2.5 kV in the language / languages: English as an attachment in your email.

The manual is 1,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3121H SMARTEC 2.5 kV

Metrel MI 3121H SMARTEC 2.5 kV User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info