MI 3108 EurotestPV Betrieb des Messgeräts
29
III
> 30
300 ms
150 ms
40 ms
IV
S
> 30
> 999 ms
500 ms
200 ms
150 ms
130 ms
60 ms
50 ms
Minimale Nichtauslösedauer
1) Mindestprüfzeitraum für den Strom von ½IN, RCD darf nicht auslösen.
2) Prüfstrom und Messgenauigkeit entsprechen den Anforderungen der AS/NZS 3017
Maximale Prüfzeiten hinsichtlich des gewählten Prüfstroms r einen selektiven
(unverzögerten) RCD.
Norm
½IN
IN
2IN
5IN
VDE 0664 (EN 61008 / EN
61009)
300 ms
300 ms
150 ms
40 ms
VDE 0100-410 TT (IEC 60364-4-
41)
1000 ms
1000 ms
150 ms
40 ms
BS 7671
2000 ms
300 ms
150 ms
40 ms
AS/NZS 3017 (I, II, III)
1000 ms
1000 ms
150 ms
40 ms
Maximale Prüfzeiten hinsichtlich des gewählten Prüfstroms r einen selektiven
(zeitverzögerten) RCD.
Norm
½IN
IN
2IN
5IN
VDE 0664 (EN 61008 / EN
61009)
500 ms
500 ms
200 ms
150 ms
VDE 0100-410 TT (IEC 60364-4-
41)
1000 ms
1000 ms
200 ms
150 ms
BS 7671
2000 ms
500 ms
200 ms
150 ms
AS/NZS 3017 (IV)
1000 ms
1000 ms
200 ms
150 ms
4.4.5 Ik-Faktor
In diesem Menü kann der Ik-Faktor zur
Berechnung des Kurzschlussstroms bei
Messungen Z-LINE und Z-LOOP gewählt
werden.
Abbildung 4.9: Wahl des Ik-Faktors
Tasten:
AUF / AB
Stellt den Ik Wert ein.
TEST
Bestätigt den Ik-Wert.
ESC
Kehrt zum Menü Einstellungen zurück.
Funktionswahltaste
Kehrt ohne Änderungen zum Hauptmenü zurück.
Der Kurzschlussstrom Ik im Versorgungssystem ist wichtig für die Auswahl oder
Überprüfung von Schutzschaltern (Sicherungen, Überstromschutzschalter, RCDs).
Der Standardwert des Ik-Faktors (ksc) ist 1,00. Der Wert sollte nach den örtlichen
Bestimmungen eingestellt werden.
Der Einstellbereich für den Ik-Faktor ist 0,20 3,00.
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3108 - Eurotest PV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3108 - Eurotest PV in the language / languages: German as an attachment in your email.

The manual is 4.94 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3108 - Eurotest PV

Metrel MI 3108 - Eurotest PV User Manual - English - 123 pages

Metrel MI 3108 - Eurotest PV User Manual - Dutch - 62 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info