5.4.1 Contact voltage (RCD Uc)
A current flowing into the PE terminal causes a voltage drop on earth resistance, i.e.
voltage difference between PE equipotential bonding circuit and earth. This voltage
difference is called contact voltage and is present on all accessible conductive parts
connected to the PE. It shall always be lower than the conventional safety limit voltage.
The contact voltage is measured with a test current lower than ½ IN to avoid trip-out of
the RCD and then normalized to the rated IN.
Contact voltage measurement procedure
Select the RCD function using the function selector keys.
Set sub-function Uc.
Set test parameters (if necessary).
Connect test cable to the instrument.
Connect test leads to the item to be tested (see figure 5.17).
Press the TEST key to perform the measurement.
Store the result by pressing the MEM key (optional).
The contact voltage result relates to the rated nominal residual current of the RCD and
is multiplied by an appropriate factor (depending on RCD type and type of test current).
The 1.05 factor is applied to avoid negative tolerance of result. See table 5.1 for detailed
contact voltage calculation factors.
RCD type
Contact voltage Uc proportional to
Rated IN
AC
1.05IN
any
AC
S
21.05IN
A, F
1.41.05IN
30 mA
A, F
S
21.41.05IN
A, F
21.05IN
< 30 mA
A, F
S
221.05IN
B, B+
21.05IN
any
B, B+
S
221.05IN
Table 5.1: Relationship between Uc and I
N
Loop resistance is indicative and calculated from Uc result (without additional
proportional factors) according to:
N
C
LI
U
R
.
Figure 5.18: Example of contact voltage measurement results
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3108 - Eurotest PV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3108 - Eurotest PV in the language / languages: English as an attachment in your email.

The manual is 3.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3108 - Eurotest PV

Metrel MI 3108 - Eurotest PV User Manual - German - 136 pages

Metrel MI 3108 - Eurotest PV User Manual - Dutch - 62 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info