MI3002 MI3100 MI3102 IT supply systems
92
B.3.2 Line impedance
See chapter 5.6 Line impedance and prospective short-circuit current, the measurement
is the same; only terminal voltage monitor indication corresponds to IT system.
B.3.3 RCD testing
RCD testing is performed in the same way as in TN/TT system (See chapter 5.4 Testing
RCDs), with the following exception:
Contact voltage measurement is not relevant.
Test circuit with bypassing principle should correspond to that in figure B.3.
L1
L2
L3
PE
R
E
Zi
L1
PE
L2
L/L1
N/L2
PE/L3
RCD
R
E2
RCD
Figure B.3: RCD testing in IT system
B.3.4 First fault leakage current (ISFL) (MI 3102 only)
First fault leakage current measurement is performed in order to verify the maximum
current that could leak into PE from observed line. This current flows through the
insulation resistance and reactance (capacitance) between the other lines and PE.
92


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3102 BT - Eurotest XE at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3102 BT - Eurotest XE in the language / languages: English as an attachment in your email.

The manual is 1.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3102 BT - Eurotest XE

Metrel MI 3102 BT - Eurotest XE User Manual - Dutch - 33 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info