10
4-FLUE
ROOF AT 60° ROOF AT 45°
SIZING
The depression (draught) of a ue depends on its height. Check the depression with the values indicated in the technical characteristics.
The minimum height of the chimney is 3.5 meters.
The interior cross-section of the ue can be round (best), square or rectangular (the ratio between the internal sides must be ≤1.5) with
the sides joined with a minimum radius of 20 mm. The dimension of the cross-section must be minimum Ø100mm.
The cross-sections/lengths of the chimneys shown in the technical data tables are indications for correct installation. Any alternative
congurations must be correctly sized in accordance with the general method of calculation of UNI EN13384-1 or other proven eciency
methods.
Below is a list of some ues available on the market:
AISI 316 steel chimney with
double chamber insulated
with ceramic bre or
equivalent resistant up to
400°C.
Refractory chimney with
double insulated chamber and
external lightweight concrete
cladding with cellular material
such as clay.
Traditional square-section
clay chimney with insulating
empty inserts.
Avoid products with an
internal rectangular section
where the larger side is 1.5
times the smaller side (e.g.
20x40 or 15x30).
EXCELLENT GOOD POOR VERY POOR
A = MIN. 2.60 metres
B = DISTANCE > 1.20 metres
C = DISTANCE < 1.20 metres
D = 0.50 metres ABOVE HIGHEST POINT
E = 2.10 metres
F = REFLUX AREA
A = MIN. 2.00 metres
B = DISTANCE > 1.30 metres
C = DISTANCE < 1.30 metres
D = 0.50 metres ABOVE HIGHEST POINT
E = 1.50 metres
F = REFLUX AREA
FIGURE 5 FIGURE 6
Downloaded from www.Manualslib.com manuals search engine
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ Thema Air - 2013 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ Thema Air - 2013 in the language / languages: English as an attachment in your email.

The manual is 5,65 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of MCZ Thema Air - 2013

MCZ Thema Air - 2013 Usermanual and installation guide - Dutch - 52 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info