32-ALARMS
Remembering that the draught recommended for the products to work properly is 10 Pa at maximum capacity and 5 Pa at minimum
(according to the technical data sheet found in the user and maintenance manual), adjustments may be required in worse draught
conditions (also due to the position of the ue in areas that are particularly subject to adverse weather such as prevailing winds, snow,
northern exposure, etc.) so as to always guarantee the required negative pressure inside the hopper.
To compensate for the lack of internal negative pressure simply adjust the speed (RPM) of the smoke extractor so as to guarantee the
minimum values of the table.
If the negative internal pressure values are noted to be lower than those indicated, this can also be due to the internal gaskets not being
sealed properly or to the product being worn over time.
OPERATING INSTRUCTIONS ON NEGATIVE PRESSURE INSPECTIONS AND POSSIBLE VARIATIONS OF THE RPM
Connect a pressure gauge to the pressure outlet on the hopper:
• For products with a specic pressure outlet in the hopper, access the sampling point and connect the pressure gauge
• For products without a dedicated pressure outlet, disconnect the tube of the pressure switch from the pressure outlet on the hopper,
add a Tee tting on the tube to intercept the circuit connecting the pressure gauge and reconnect the tube to the pressure outlet on
the hopper.
Possible adjustments of combustion and consequently of the negative pressure inside the hopper can be implemented in two ways:
A) Changing the RPM value of the smoke extractor in the SETTINGS MENU
• The available values are from -3 to +3 which, as a percentage, correspond to:
• RPM: -10% +10% in Active System products
• RPM: -30% +50% in NON-Active System products
• The percentage variation aects all power values (1 to 5) proportionally and as a percentage. The percentage variation does not aect
intermediate operating stages such as SWITCH ON, FIRE ON or SWITCH OFF
• As the RPM increases, suction also increases and consequently the internal negative pressure, thereby compensating the phenomena
that trigger the alarm.
B) Adjusting the RPM of the gear motor manually in the TECHNICAL PARAMETERS MENU
• The pressure switch has a calibration of 10/20 Pa which means that it trips when the negative pressure inside the hopper drops below
10 Pa and requires more than 20 Pa negative pressure inside the hopper for it to reset
• The negative pressure value at the minimum power must always be higher than 10 Pa while also maintaining a reasonable margin
that can worsen over time due to the gaskets or similar being worn (at least 12/13 Pa)
• The negative pressure at maximum power must always be above 20 so that the pressure switch can reset when the pressure switch
resetting the automated device is activated. The pressure switch resetting procedure (such as after opening the cover to top-up
the hopper), requires the electronics to push the RPM of the smoke extraction fan up to POWER 5 (P5) for a few moments. At P5,
therefore, the negative pressure inside the hopper must always be > 20 Pa (recommended 22/23 Pa to preserve the margin).
• PLEASE NOTE = The TECHNICAL PARAMETERS menus are password-protected to prevent the user from accessing them
inadvertently and are not visible in the user menus.
Attention! The factory setting on the product is designed to obtain the certied technical data. With a data
discrepancy (such as the pellet recipe), the settings may be modied as explained above.
The adjustments must only be carried out by authorised and qualied personnel under their responsibility and by
checking the conformity of the installation beforehand.
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ SUITE AIR 10 M2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ SUITE AIR 10 M2 in the language / languages: English as an attachment in your email.

The manual is 11.72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of MCZ SUITE AIR 10 M2

MCZ SUITE AIR 10 M2 Installation Guide - English - 68 pages

MCZ SUITE AIR 10 M2 User Manual - German - 72 pages

MCZ SUITE AIR 10 M2 Installation Guide - German - 68 pages

MCZ SUITE AIR 10 M2 User Manual - Dutch - 72 pages

MCZ SUITE AIR 10 M2 Installation Guide - Dutch - 68 pages

MCZ SUITE AIR 10 M2 User Manual - French - 72 pages

MCZ SUITE AIR 10 M2 Installation Guide - French - 76 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info