PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page 46
Operation Technical service - Rights reserved MCZ Group S.p.A. - Reproduction prohibited
Failure when carrying out works of maintenance,
cleaning and repair to adopt all necessary measures and
precautions
Tampering with the safety devices.
Removing the safety devices.
Failure to connect the stove to an efficient system for the
discharge of smoke.
Failure to check in advance that the room where the
stove is to be installed is adequately ventilated.
7.2. ALARM SIGNALLING
If there is an operating anomaly, the stove goes into alarm shutdown
mode and informs the user of the type of problem that has occurred via
a 3-figure code displayed on the rear emergency panel.
The alarm is permanently signalled by the corresponding 3-figure code,
by a flashing red light on the emergency panel, and, for the first ten
minutes of the alarm, by a periodic acoustic signal. To take the stove
out of alarm conditions and restore its normal operation, read the
instructions in the next two paragraphs.
The table below describes the possible alarms signalled by the stove,
associated to the respective code that appears on the emergency
panel, and useful suggestions to solve the problem.
MESSAGE ON
DISPLAY
TYPE OF PROBLEM SOLUTION
A01
Fire fails to ignite
Check the level of pellets in the hopper.
Check that the grate is properly inserted in its housing
and does not have any obvious unburnt incrustations;
Check whether the ignition plug heats.
A02
Fire extinguishes abnormally
It derives from a shutdown due to lack of fuel (hopper
empty).
A03
Pellet tank temperature exceeds foreseen
safety limit.
Overheating of the stove body
The structure is too hot because the product has been
operating for too long at maximum power, or it is
poorly ventilated, or the air fans are faulty. When the
stove is sufficiently cold, press button B of the control
panel or OFF on the remote control to cancel the alarm
A03. Once the alarm is cancelled it is possible to relight
the stove normally.
A04
T
he temperature of the smoke discharge has
exceeded pre-set safety limits
T
he stove will shut off automatically. Let the stove cool
off for a few minutes, then re-light it.
Check smoke release and the type of pellet being used.
A05
Flue pipe obstruction - wind - door open.
Check fume conduit and door closure.
A06
T
he smoke extractor is not able to provide the
primary air required for combustion.
Draught difficulties or clogging of grate.
Check whether the grate is clogged by incrustation and
clean as required.
Control and if necessary clean the smoke duct and the
air intake.
A08
Flue-gas exhaust fan broken
Check that the smoke fan compartment is clean and if it
is dirt that is blocking it.
If insufficient, the smoke fan is defective. Call an
authorized service centre to make the replacement.
A09
T
he smoke probe is defective and does not
properly measure the temperature of the
discharge smoke
Contact an authorized service centre to replace the
component.
Downloaded from www.Manualslib.com manuals search engine
46


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ Nima Air 2011 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ Nima Air 2011 in the language / languages: English as an attachment in your email.

The manual is 4,32 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info