33-ALARMS
Technical Dept. - All rights reserved - Reproduction prohibited
If alarm A21 is triggered often, please note that:
A21
PRESSURE
SWITCH
Stove door open Close the door
Fuel loading hatch open Close the hatch.
Lower the fuel level in the hopper.
Air pressure switch Draught diculties or clogged brazier.
Check whether the brazier is clogged by deposits and clean it, if
necessary.
Check and if necessary clean the smoke duct and air inlet.
it is required to check some points to verify the cause of the problem and potentially operate on some adjustments and/or safety devices
to restore correct operation of the product.
However please note that all adjustments and alterations aecting the operational safety devices, must only be performed if THE
PRODUCT IS INSTALLED IN COMPLIANCE WITH THE STANDARDS AND LAWS IN FORCE AND IF IT IS SERVICED PROPERLY BY AUTHORISED AND
SPECIALISED PERSONNEL. Alterations performed randomly, to ensure operation of the product even under non-compliant conditions, can
cause serious damage to property and injuries to people.
Attention!
The adjustments must only be carried out by authorised and qualied personnel under their responsibility and
by checking the conformity of the installation beforehand. The manufacturer declines all liability for damage to
property or injuries to people if the safety devices are altered.
All liability for improper use of the product is entirely borne by the user and relieves the manufacturer from any civil
and criminal liability.
Series of stoves equipped with a pressure switch installed on the hopper with the sampling point positioned on the bottom, to the right of
the gear motor. This system protects the whole system ensuring airtightness of the stove throughout its duration.
It is important to understand that the pressure switch can be triggered with each signicant drop in negative pressure and may be due to:
• Flue clogging.
• The presence of a foreign body in the ue (birds, nests, clogged grilles, etc.).
• Wind coming through the ue because it is unprotected or the installation was wall-mounted or required no ue.
• Cold air draught down the ue.
• A damaged pressure switch.
• Blocked membrane inside the pressure switch because soot or pellet dust got in.
• The pellet hopper is open or ajar for more than 60 seconds (60 seconds is the estimated time to reload the hopper).
• Pellets trapped between the hopper cover and the hopper, which prevents the gasket from sealing.
• Broken/worn hopper cover gasket.
• The gasket between the feed screw and the boiler is damaged or positioned incorrectly.
• Fire door is open or the gasket is worn.
• Clogged lateral smoke exchangers.
• Inspection caps with gaskets installed incorrectly after maintenance.
• Feed screw clogged by compressed pellets at the top.
• The installation is compliant and the ue/smoke tting does not generate obvious obstructions which can stop the release of smoke,
such as: long horizontal sections (over 3 metres), uninsulated smoke ducts, “wall-mounted” smoke exhaust without proper terminals
(installation regulated and permitted in France only [ZONE 3])
• Internal air extraction or recirculation systems (e.g. VMC systems) that generate internal negative pressure exceeding the value
required by law (not exceeding 4 Pa)
• Installed without combustion air ducting, it is crucial to check that there is an ecient air inlet dedicated to the stove, according to
the specications referred to in chapter 2 of this manual.
The circuit board has also been equipped with an automatic device with a timer and contactors which increase the RPM of the smoke
extractor so as to restore the negative pressure inside the hopper and therefore the pressure switch, if the cover is opened for top-up or if
there is an immediate or occasional pressure drop such as gusts of wind outside. If the pressure drop lasts for more than 60 seconds, the
product goes into alarm status (A05 or A18)
53


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ MUSA COMFORT AIRMATIC 14 M2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ MUSA COMFORT AIRMATIC 14 M2 in the language / languages: English as an attachment in your email.

The manual is 12.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of MCZ MUSA COMFORT AIRMATIC 14 M2

MCZ MUSA COMFORT AIRMATIC 14 M2 Installation Guide - English - 64 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 User Manual - German - 72 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 Installation Guide - German - 64 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 User Manual - Dutch - 72 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 Installation Guide - Dutch - 64 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 User Manual - French - 72 pages

MCZ MUSA COMFORT AIRMATIC 14 M2 Installation Guide - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info