643532
17
Zoom out
Zoom in
Previous page
1/72
Next page
15
2-INSTALLATION
Technical Dept. - All rights reserved - Reproduction is prohibited
DISTANCE (metres) The air inlet must be at a distance of:
1.5 m BELOW Windows, doors, smoke outlets, cavities, ....
1.5 m HORIZONTALLY Windows, doors, smoke outlets, cavities, ....
0.3 m ABOVE Windows, doors, smoke outlets, cavities, ....
1.5 m AT A DISTANCE from smoke outlet
CONNECTION TO THE FLUE
The connection between the ue and the appliance must be via a smoke duct that conforms with EN 1856-2. The connecting section must
extend no more than 4 m horizontally, with a minimum slope of 3% and with a maximum of 3 90% bends (accessible for inspection - do
not count the T tting at the appliance outlet).
The diameter of the smoke duct must be equal to or greater than that of the outlet of the appliance (Ø 80 mm).
TYPE OF SYSTEM SMOKE DUCT
Minimum vertical length 1.5 metres
Maximum length
(with 1 accessible 90° bend)
6.5 metres
Maximum length
(with 3 accessible 90° bends)
4.5 metres
Maximum number of accessible 90° bends 3
Horizontal sections
(minimum slope 3%)
4 metres
Use smoke ducts with a diameter of 80mm or 100mm depending on the type of system, with silicone gaskets or similar gaskets that can
withstand the high operating temperatures of the appliance (min. T200 class P1). The use of exible metal hoses made of bre
cement or aluminium is forbidden. For direction changes, we always recommend the use of a T tting with an inspection cap
allowing easy access for cleaning the tubes. Always ensure that the inspection cap is put back in place and sealed hermetically with the
relevant seal intact after cleaning.
It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from hoods above it. It is forbidden to extract
the combustion products directly through the wall, whether into indoor spaces or outdoors.
The smoke duct must be at a minimum distance of 400 mm from ammable or heat-sensitive structures.
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ Mood COMFORT AIR at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ Mood COMFORT AIR in the language / languages: English as an attachment in your email.

The manual is 6,79 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info