2-INSTALLATION
FOREWORD
This chapter on the Smoke Flue has been produced in reference to the prescriptions of European regulations (EN13384 - EN1443 - EN1856
- EN1457).
The chapter provides indications for installing an ecient and correct smoke ue but is under no circumstances to substitute the
regulations in force, which the qualied technician must be in possession of. Check with local authorities whether there are any restrictive
regulations in force regarding the intake of air for combustion, the smoke extraction system, the ue or the chimney.
The company declines all liability relating to the poor functioning of the boiler if this is due to the use of an insuciently sized ue in
violation of regulations in force.
SMOKE FLUE
The ue or chimney is of great importance for the proper operation of a solid fuel-burning heating appliance with natural draught, as
modern heating appliances have high eciency with cooler ue gasses and consequently less draught, it is therefore essential that the
ue is built up to standard and always kept in perfect working order. A ue that serves a pellet/wood fuelled appliance must be at least
category T400 (or greater if the appliance requires, and resistant to soot res. Smoke must be extracted through a single ue made of
insulated steel (A) or an existing ue that complies with the intended use (B).
A simple air shaft in cement must be suitably lined. In both solutions there must be an inspection cap (AT) and/or inspection hatch (AP)
- FIG.1.
It is prohibited to connect more than one wood/pellet or any other type of appliance (vent cowling...) to the same ue.
FIGURE 1 - SMOKE FLUE