15
2-INSTALLATION
Technical Dept. - All rights reserved - Reproduction is prohibited
DISTANCE (metres) The air inlet must be at a distance of:
1.5 m UNDER Windows, doors, smoke outlets, cavities, ....
1.5 m HORIZONTALLY Windows, doors, smoke outlets, cavities, ....
0.3 m ABOVE Windows, doors, smoke outlets, cavities, ....
1.5 m AWAY from smoke outlet
CONNECTION TO FLUE
The connection between the ue and the appliance must be via a smoke duct that conforms with EN 1856-2. The connecting section
must extend no more than 4 m horizontally, with a maximum incline of 3% and containing a maximum of 3 90% bends (accessible for
inspection - do not count the T joint at the appliance outlet).
The diameter of the smoke duct must be equal to or greater than that of the appliance outlet (Ø 80 mm).
TYPE OF DEVICE SMOKE DUCT
Minimum vertical length 1.5 metres
Maximum length
(with 1 accessible 90° bend)
6.5 metres
Maximum length
(with 3 accessible 90° bends)
4.5 metres
Maximum number of accessible 90° bends 3
Horizontal sections
(minimum incline 3%)
4 metres
Use smoke ducts with a diameter of 80mm or 100mm depending on the type of system, with silicone gaskets or similar gaskets that can
withstand the high operating temperatures of the appliance (min. T200 class P1). The use of exible metal tubes in bre cement
or aluminium is prohibited. For direction changes, we always recommend the use of a T joint with an inspection cap allowing
easy access for cleaning the tubes. Always ensure that the inspection cap is replaced and hermetically sealed with the seal in tact after
cleaning.
It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from overhead cowling. It is prohibited to
extract the products of combustion directly through the wall, whether into indoor spaces or outdoors.
The smoke duct must be a minimum distance of 400 mm from ammable or heat-sensitive structures.