2-INSTALLATION
ROOF AT 60° ROOF AT 45°
SIZING
The negative pressure (draught) of a ue also depends on its height. Check the negative pressure with the values indicated in the technical
specications. The minimum height of the chimney is 3.5 metres.
The interior cross-section of the ue can be round (best solution), square or rectangular (the ratio between the internal sides must be
≤1.5) with the sides joined with a minimum radius of 20 mm. The dimension of the cross-section must be minimum Ø100mm.
The cross sections/lengths of chimneys must be correctly sized in accordance with the general method of calculation of UNI EN13384-1 or
other proven eciency methods.
Some examples of ues available on the market are provided below:
AISI 316 steel chimney with
double chamber insulated with
ceramic bre or equivalent
resistant up to 400°C.
Refractory chimney with
double insulated chamber and
external lightweight concrete
cladding with cellular material
such as clay.
Traditional square-section clay
chimney with insulating empty
inserts.
Avoid products with an internal
rectangular section where the
larger side is 1.5 times the
smaller side (e.g. 20x40 or
15x30).
EXCELLENT GOOD POOR VERY POOR
A = MIN. 2.60 metres
B = DISTANCE > 1.20 metres
C = DISTANCE < 1.20 metres
D = 0.50 metres ABOVE HIGHEST POINT
E = 2.10 metres
F = REFLUX AREA
A = MIN. 2.00 metres
B = DISTANCE > 1.30 metres
C = DISTANCE < 1.30 metres
D = 0.50 metres ABOVE HIGHEST POINT
E = 1.50 metres
F = REFLUX AREA
FIGURE 5 FIGURE 6
16


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for MCZ AKI HYDROMATIC 24 M1 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of MCZ AKI HYDROMATIC 24 M1 in the language / languages: English as an attachment in your email.

The manual is 4.67 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of MCZ AKI HYDROMATIC 24 M1

MCZ AKI HYDROMATIC 24 M1 User Manual - English - 64 pages

MCZ AKI HYDROMATIC 24 M1 User Manual - German - 64 pages

MCZ AKI HYDROMATIC 24 M1 Installation Guide - German - 52 pages

MCZ AKI HYDROMATIC 24 M1 Installation Guide - Dutch - 48 pages

MCZ AKI HYDROMATIC 24 M1 User Manual - Dutch - 64 pages

MCZ AKI HYDROMATIC 24 M1 Installation Guide - French - 48 pages

MCZ AKI HYDROMATIC 24 M1 User Manual - French - 64 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info