Refrigerant Piping Connection
6
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters (16.5ft).
Refer to the table below for specifications on the maximum length and drop height of piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model Capacity (BTU/h) Max. Length (m) Max. Drop Height (m)
R410A Inverter Split Air
Conditioner
< 15,000 25 (82ft) 10 (33ft)
15,000 and < 24,000 30 (98.5ft) 20 (66ft)
24,000 and < 36,000 50 (164ft) 25 (82ft)
36,000 and 60,000 65 (213ft) 30 (98.5ft)
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care
to cut and flare them properly. This will ensure
efficient operation and minimize the need for
future maintenance.
1. Measure the distance between the indoor and
outdoor units.
2. Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle. Refer to Fig. 6.1 for bad cut examples.
Oblique Rough Warped
90°
Fig. 6.1
Refrigerant
Piping
Connection
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Maxicool Luna - LMD-AE-18HDI at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Maxicool Luna - LMD-AE-18HDI in the language / languages: English as an attachment in your email.

The manual is 9,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Maxicool Luna - LMD-AE-18HDI

Maxicool Luna - LMD-AE-18HDI Additional guide - English - 8 pages

Maxicool Luna - LMD-AE-18HDI User Manual - English - 19 pages

Maxicool Luna - LMD-AE-18HDI Additional guide - Dutch - 16 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info