EN / MasterBus – CANopen Interface 5
Data type
Data on CANopen can be represented as a float or
as a 16 bit Integer.
Floats store float-point values, that is, values that
have potential decimal places.
Integers use 2 bytes and only store integral values,
that is whole numbers.
Which type you chose depends on the capabilities of
the receiving CANopen product.
Scaling
When using Integer values on CANopen you might
want to use scaling. This allows values like the
battery voltage to be transmitted without losing
accuracy. Select Scaling ‘x100’ to transmit a value
1325 instead of 13,25.
When receiving a CANopen PDO the input value will
be divided by the scaling value.
Select ‘x1’ if you don’t need scaling.
4.4 DATA FIELD CONFIGURATION
(ADVANCED)
It is also possible to update the data field
configurations directly by changing the strings in
‘Data fields A’ group and ‘Data Fields B’ group.
The complete configuration of each data field is
shown as a string ( sequence of characters).
These strings look like Figure 3 and consist of five
parts: the CANopen configuration, the data direction,
the MasterBus configuration, a comma separator
and the data representation.
Figure 3. Example of configuration string
NOTE: you will notice the same configuration
parameters as in the configuration via the standard
method but now combined into one string.
Meaning:
285
This is the hexadecimal COB-ID of the CANopen
message. Range: 0x181 –0x57F.
b0 Byte followed by the location of the data within
the PDO. Minimum value is 0, maximum value is
6.
< Direction indicator. “<” indicated data direction
from MasterBus to CANopen. “>” indicates data
direction from CANopen to MasterBus
1 Device Number. The device in the Device
numbers group with this number will be used to
connect to. Minimum number 1, maximum
number 20.
m Indicates data on the monitoring page is used.
Other options include a(Alarm page),
c(Configuration page) and h (History page)
0 Index on page. Decimal value ranging from 0 to
1000.
, Comma separator
s Indicates data on CANopen is represented as 2
byte signed int. Other option is f (Float) for a 4
byte float representation.
0 Indicates data scaling on CANopen. Use 0 for no
scaling(x1).
1 for ‘x10 scaling, 2 for x100 scaling and 3 for
x1000 scaling on CANopen.
4.5 CONFIG ERROR
Your CANopen interface status will show ‘Config
Error’ if:
1. Two or more data fields are ‘CANopen<MB’
and have the same COB-ID and the data is
overlapping.
2. One or more data fields are CANopen>MB
and do not fit in the 8 data bytes.
When there is a ‘Config error’ no CANopen PDO’s
will be transmitted or received by the CANopen
interface.
285b0<1m0,s0
Figure 4:
Example of stings in advanced data field
configuration
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mastervolt MasterBus CANopen Interface at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mastervolt MasterBus CANopen Interface in the language / languages: English as an attachment in your email.

The manual is 0.22 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info