measured and adjusted on the damper for the nominal
value.
Free blowing, the capacity in kg/h will increase: If the
demand for very dry air is not needed, the dehumidier
should then operate free blowing
the reg.– air ow can be adjusted on the damper in
the reg.–air outlet (option). Start–up with the damper
in the closed position, opening until the Ammeter in-
dicates:
DHA140: 3A, DHA250:6A, DHA360: 8A
Notice: DHA140 has no Ammeter installed and the Amp
must be measured using an Ampere instrument.
IMPORTANT :
Reg.–air ow always has to be controlled. Check the
reg.–duct for allowing free blowing of the reg.–air.
Check that the reg.–air duct is installed draining from the
dehumidier.
SPECIAL FOR DHA360:
STARTING–UP OF THE HEATERS:
The two heaters E1 & E2 starts up with 10K4 delaying
E1 with 30 seconds.
On the Am–meter this will be indicated like this:
when the dehumidier is switched on, the Am.meter
shows 10A in app. 5 sec., and fall down to 5A.
after 30 sec. E1 is switched on and the Ammeter
show app. 18A for 5 sec., and then it fall down to
8,00A with the reg–air correctly adjusted.
With the electrical settings and air ows adjusted, the
dehumidier will then operate automatically by means of
the internal control– and safety functions – controlled by
an external hygrostat.
7. MAINTENANCE
The DHA dehumidiers only needs a minimum of main-
tenance. All components are service free, which means
no lubrication or adjustment.
Only three things should be checked under normal ope-
ration:
air lter should be replaced at least every 2 months
if stationary installed. At renting the dust level might
be high and the lter must be replaced often and
the cabinet and rotor should be cleaned after each
period,
the rotation of the rotor should be checked once a
month,
the power consumption of the electric heater should
be checked often (reading on the Ammeter, Excl.
DHA140)).
Rotation of the rotor can be checked through the dry air
outlet if no duct is connected). The rotor should then turn
clockwise.
If the rotor rotates during operation, and the energy con-
sumption of the electric heater shows nominal Amp, you
can be almost sure that the dehumidier is operating at
an optimum. We nevertheless recommend some peri-
odic verication of the entire dehumidier, to see if all
internal functions are OK and checking of gaskets and
moving parts for wear and tear.
This will ensure that the capacity is on its maximum, and
thus won’t waste any energy.
8. TROUBLE SHOOTING
IF THE DEHUMIDIFIER DOES NOT START
WHEN ELECTRIC CONNECTED:
check the external fuse
IF THE DEHUMIDIFIER IS NOT OPERA-
TING IT IS PROBABLY THE EXTERNAL
HYGROSTAT WHICH HAS BROKEN:
This is a normal situation when the desired humidity
is obtained. To check: adjust the hygrostat for 20%RH,
and the dehumidier should start operating. Adjust again
for the desired humidity.
IF THE DESIRED HUMIDITY IS NOT OB-
TAINED:
The problem can be the dehumidier or the oth-
er parts in the total installation ( room tightness, hyg-
rostat...). To verify this, check:
rotation of rotor ?
the dry air should be 15–20°C warmer than the inlet
main air. If it is cold it could indicate that the rotor is
not turning caused by broken drive belt or the motor
has stopped.
by hand feel the temperature of the reg. outlet air, and
feel the airow. The temperature is depending on the
inlet conditions, but should be 40–60°C.
If the temperature is higher it could indicate that the
rotor is not turning.
Check the Ammeter reading, must be nominal value:
DHA140: 3A *), DHA250:6A, DHA360: 8A
*) no Ammete
If it is cold and Ammeter shows 0A, the electric heater
might need replacement.
THE UNIT IS TOO NOISY:
Check whether the unit is sitting on a level surface.
THE UNIT IS LEAKING:
Make sure the unit is in good shape.
If you are not using continuous drainage, make sure
the rubber plug (at the bottom of the unit) is in its posi-
tion.
9. SERVICE/REPAIR
SAFETY INSTRUCTION
Before opening the dehumidier, make sure that the
electric power is switched off on the main switch. Pull
the power plug to be sure.
REPLACING THE ELECTRIC HEATERS
DHA140:
Remove the cabinet top cover.
Remove the internal hose for the reg–air outlet.
Release the total internal assembly, and pull it out of the
cabinet.
The PTC heater is now accessible for replacing.
DHA250, DHA360:
When the small cover in the front of the dehumidier is
removed, the two PTC heaters are accessible for repla-
cing.
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for master DHA 250 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of master DHA 250 in the language / languages: All languages as an attachment in your email.

The manual is 2,33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info