16 Operating Instructions, Comfort 580 GB (#91636)
6. Installation
6.7 Connection of control elements
Attention!
In order to avoid damaging the
controls:
- The local safety regulations must be
complied with at all times.
- It is very important that mains cables
are laid separately from control cables.
- The controls voltage must be 24 V DC.
- If external voltages are applied at
terminals XM70A, XV51A, XM70B,
XV51B, XB99, XP54B, XP54A, XP62B,
XP62A or XB70, the entire electronic
system will be destroyed.
- Only potential-free contacts may be
connected to terminals B9, 5, 34, 3
and 8 (XB99).
- The connections XM70B and XV51B
are not to be used!
Caution!
Danger of electric shock:
Before any cabling works begin, it must
be ensured that the cables are
disconnected from the power supply.
During cabling works, it must be
ensured that the cables remain
disconnected from the power supply at
all times (e.g. prevent reconnection).
Label Type / function
XB70 Connection of modular antenna 8.1
XB99
Connection of external control
elements
6.7 / 2
6.7 / 3
6.7 / 4
6.7 / 5
XH01
Connection for programmable
output 16/17 (e.g. signal light,
24 V DC, 0,5 A)
Wiping impulse 15/16
6.7 / 6
6.7 / 7
XM70A
Connection for motor unit
(MASTER)
6.8 / 4
6.8 / 7
XM70B
Connection for motor unit
(SLAVE)
6.8 / 4
6.8 / 7
XN70
Connection Battery Backup
(if available)
-
XN81 Connection for mains cable
6.7 / 6
6.9
XP54A
Connection for closing edge
safety device, gate travelling
direction CLOSE
6.7 / 8
XP54B
Connection for closing edge
safety device, gate travelling
direction OPEN
6.7 / 8
XP62A
Connection for photocell,
gate travelling direction CLOSE
6.7 / 9
XP62B
Connection for photocell,
gate travelling direction OPEN
6.7 / 9
XV51A
Connection for rpm detector
and reference point sensor
(MASTER)
6.8 / 3
6.8 / 7
XV51B
Connection for rpm detector
and reference point sensor
(SLAVE)
6.8 / 3
6.8 / 7