5. Initial Operation of Control Unit Control 144 / 145 / 145 FU
English / Page 13
Attention!
The control units Control 144 / 145 / 145 FU feature a static
current circuit. If this static current circuit is interrupted, power
operation of the door is no longer possible. Elements within
this static current circuit are e.g. the cable slack switch, the wicket door switch
and cable safety switch. If these elements are not available, insert enclosed
short-circuit plug into socket X30.
5.2 Connection control unit - door leaf
Attention!
If you want to put a door system with closing edge safety
device into operation, please pass on according to wiring
diagram mentioned on page 52 (fig. 18) insted of wiring
diragram mentioned below.
For following operational check the optosensor (transmitter and receiver) may
not be connected.
Connection of cable slack device (all except Dynamic 300 - 301)
• Connect system cable to socket X30 in control unit.