30
Fault
No voltage.
No response on
impulse.
Remote control.
Power limit.
Door can only be
opened.
Door can only be
closed in dead man's
mode (press-and-hold)
Operator starts up
then stops.
No function.
Signal/message
VOLTAGE control does not light
up
Error message 0 displayed.
REMOTE CONTROL control light
does not flash on impulse from
hand transmitter.
Error message 10 displayed.
Error message 15 displayed.
Error message 24 displayed.
REMOTE CONTROL control light
does not light up when
reference point passed.
Error message 13 displayed.
Red control light on optosensor
circuit board does not light up.
Error message 9 displayed.
Error message 29 or 30
displayed.
Cause
No voltage.
Emergency hand chain is not in the home
position.
Operator is disengaged.
Thermal overload protection engaged.
Control unit is locked
(red mark).
Static current circuit (control elements) is
open.
Static current circuit (door leaf) is open.
Electronic aerial is disconnected.
Hand transmitter incorrectly coded.
Flat battery.
Power limit set too sensitive.
Door operation too sluggish.
S20 programming switch at OFF,
but no photocell connected.
S20a programming switch at OFF, but no
photocell connected.
Reference point switch at wrong setting.
Optosensor is disconnected.
Coiled cable defective.
Optosensors are not in the bottom door seal
or are defective.
Bottom door seal is deformed.
RPM sensor defective.
Fault in the control unit.
Remedy
Check voltage. Check main fuses in the electric distribution, 4 amp
fuse in the control unit and the mains plug connection.
Return the emergency hand chain to the home position
(see Operllation Instructions).
Engage the maintenance release or quick release.
Allow the motor to cool down.
Unlock control unit (blue mark).
Insert short-circuit plug or control element plug into X10 socket.
Connect the STOP button to terminals 13 and 13.
Check cable slack switch, wicket door switch and cable safety switch
Coonect aerial (see page 17).
Recode the hand transmitter (see page 17).
Insert new 9V battery ( IEC 6F22).
Make power limit less sensitive (see page 11).
Door system requires maintenance (lubrication or similar).
Switch over S20 programming switch or connect photocell.
Switch over S20a programming switch or connect photocell.
Alter reference point setting (see page 9).
Connect optosensor (see page 13).
Check coiled cable and connections.
Check that optosensors are correctly installed or, if necessary,
replace.
Align bottom door seal or, if necessary, replace.
Have drive unit checked.
Have control unit checked.
6. Appendix
6.2 Test instructions