696199
25
Zoom out
Zoom in
Previous page
1/88
Next page
ENGLISH
CONNECTION TO THE CHIMNEY
Products with automatic door closing (type 1) must operate, for safety reasons, with the furnace door closed (except during the fuel loading
or ash removal phases).
Products with non-automatic door closing (type 2) must be connected to their own ue.
Operation with doors open is only allowed when supervised.
The connection pipe to the ue must be as short as possible, straight horizontal and positioned slightly in ascent, and watertight.
Connection must be carried out with stable and robust pipes,comply with all current Standards and Regulations and to those envisioned by
the law, and be hermetically secured to the ue. The internal diameter of the connection pipe must correspond to the external diameter of
the appliance ue gas exhaust stub pipe (DIN 1298).
ATTENTION: as far as concern the realisation of the ue connection and ammable materials please follow the requirements
provided by UNI 10683 standard. The ue must be properly spaced from any ammable materials or fuels through a proper
insulation or an air cavity. Minimum distance safety 25 cm.
The chimney pressure (DRAUGHT) must be at least (see chap. TECHNICAL DATA SHEET) Pascal. The measurement has always to be carried
out with hot device (rated thermal performance).
When the depression exceeds 17 20 Pa (=1.7 =2 mm of column of water), it is necessary to reduce the same by installing an additional draught
regulator (buttery valve) on the exhaust pipe or in the chimney, according to the regulations in force.
For correct appliance operation, it is essential that sucient air for combustion is introduced into the place of installation (see
paragraph VENTILATION AND AERATION OF THE INSTALLATION PREMISES).
CONNECTING A FIREPLACE OR OPEN HEARTH TO THE FLUE
The ue gas channel is the stretch of piping which connects the product to the ue. In the connection, these simple but extremely important
principles must be respected:
under no circumstances use a ue gas channel with a diameter less than that of the exhaust clamp with which the product is equipped;
each metre of the horizontal stretch of the ue gas channel causes a slight loss of head which must be compensated if necessary by
elevating the ue;
the horizontal stretch must never exceed 2 metres (UNI 10683);
each bend of the ue gas channel slightly reduces the ue draught which must be compensated if necessary by elevating it suitably;
The UNI 10683 ITALY regulation requires that under no circumstances must there be more than 2 bends or variations in direction
including the intake into the ue.
If the user wishes to use the ue as a replace or open hearth, it is necessary to seal the hood below the entrance point of the ue gas channel
pos. A Picture 5.
If the ue is then too big (e.g. 30x40cm or 40x50cm), it is necessary to intubate it with a stainless steel tube with a diameter of at least 200mm,
pos. B, taking care to close the remaining spaces between the pipe and the ue immediately under the chimney pot pos. C.
VENTILATION AND AERATION OF THE INSTALLATION PREMISES
As the product draw their combustion air from the place of installation, it is MANDATORY that in the place itself, a sucient quantity of air is
introduced. If windows and doors are airtight (e.g. built according to energy saving criteria), it is possible that the fresh air intake is no longer
guaranteed and this jeopardises the draught of the appliance and your health and safety.
IMPORTANT: For a better comfort and corresponding oxygenation of environment, the combustion air can be directly withdrawn at the
outside through a junction which is to be connected with a exible pipe. The connection pipe (not furnished) must be at with a minimum
diameter of Picture 9, a maximum length of 3 m and with no more than 3 bends. If there is a direct connection with the outside it must be
endowed with a special windbreak.
There MANDATORY be sucient quantity of air for combustion and re-oxygenation of the room to ensure the device will work properly.
There should therefore be vents letting air in from outside the building and enabling circulation of air for combustion even when the doors
and windows are closed.
The air inlets must meet the following requirements:
they must be protected with grids, metal mesh, etc., but without reducing the net useful section;
they must be made so as to make the maintenance operations possible;
positioned so that they cannot be obstructed;
Any extractor hoods in the room where the device is installed must not operate at the same time as this could cause smoke to enter the
room, even with the replaces door closed.
The clean and non-contaminated air ow can also be obtained from a room adjacent to that of installation (indirect aeration and ventilation),
as long as the ow takes place freely through permanent openings communicating with the outside.
The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a re hazard, bathroom, bedroom
or common room of the building.
25
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for La Nordica Rossella Plus Forno Evo at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of La Nordica Rossella Plus Forno Evo in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 5,95 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of La Nordica Rossella Plus Forno Evo

La Nordica Rossella Plus Forno Evo User Manual - Dutch - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info