811797
30
Zoom out
Zoom in
Previous page
1/100
Next page
ENGLISH
FOR CORRECT APPLIANCE OPERATION, IT IS ESSENTIAL THAT SUFFICIENT AIR FOR COMBUSTION IS INTRODUCED INTO THE
PLACE OF INSTALLATION (see paragraph VENTILATION AND AERATION OF THE INSTALLATION PREMISES).
CONNECTINGAFIREPLACEOROPENHEARTHTOTHEFLUE
The ue gas channel is the stretch of piping which connects the product to the ue. In the connection, these simple but extremely important
principles must be respected:
• UNDER NO CIRCUMSTANCES USE A FLUE GAS CHANNEL WITH A DIAMETER LESS THAN THAT OF THE EXHAUST CLAMP WITH WHICH THE
PRODUCT IS EQUIPPED;
• EACH METRE OF THE HORIZONTAL STRETCH OF THE FLUE GAS CHANNEL CAUSES A SLIGHT LOSS OF HEAD WHICH MUST BE COMPENSATED
IF NECESSARY BY ELEVATING THE FLUE;
• THE HORIZONTAL STRETCH MUST NEVER EXCEED 2 METRES (UNI 10683);
• EACH BEND OF THE FLUE GAS CHANNEL SLIGHTLY REDUCES THE FLUE DRAUGHT WHICH MUST BE COMPENSATED IF NECESSARY BY
ELEVATING IT SUITABLY;
• THE UNI 10683 – ITALY REGULATION REQUIRES THAT UNDER NO CIRCUMSTANCES MUST THERE BE MORE THAN 2 BENDS OR VARIATIONS
IN DIRECTION INCLUDING THE INTAKE INTO THE FLUE.
If the user wishes to use the ue as a replace or open hearth, it is necessary to seal the hood below the entrance point of the ue gas channel
pos. A Picture5.
If the ue is then too big (e.g. 30x40cm or 40x50cm), it is necessary to intubate it with a stainless steel tube with a diameter of at least 200mm,
pos. B, taking care to close the remaining spaces between the pipe and the ue immediately under the chimney pot pos. C.
VENTILATIONANDAERATIONOFTHEINSTALLATIONPREMISES
AS THE PRODUCT DRAW THEIR COMBUSTION AIR FROM THE PLACE OF INSTALLATION, IT IS MANDATORY THAT IN THE PLACE ITSELF, A
SUFFICIENT QUANTITY OF AIR IS INTRODUCED. IF WINDOWS AND DOORS ARE AIRTIGHT (E.G. BUILT ACCORDING TO ENERGY SAVING CRITERIA),
IT IS POSSIBLE THAT THE FRESH AIR INTAKE IS NO LONGER GUARANTEED AND THIS JEOPARDISES THE DRAUGHT OF THE APPLIANCE AND YOUR
HEALTH AND SAFETY.
IMPORTANT:For a better comfort and corresponding oxygenation of environment, the combustion air can be directly withdrawn at the
outside through a junction which is to be connected with a exible pipe. The connection pipe (not furnished) must be at with a minimum
diameter of Picture10, a maximum length of 3 m and with no more than 3 bends. If there is a direct connection with the outside it must be
endowed with a special windbreak.
THERE MANDATORY BE SUFFICIENT QUANTITY OF AIR FOR COMBUSTION AND RE-OXYGENATION OF THE ROOM TO ENSURE THE DEVICE WILL
WORK PROPERLY. There should therefore be vents letting air in from outside the building and enabling circulation of air for combustion even
when the doors and windows are closed.
The air inlets must meet the following requirements:
• THEY MUST BE PROTECTED WITH GRIDS, METAL MESH, ETC., BUT WITHOUT REDUCING THE NET USEFUL SECTION;
• THEY MUST BE MADE SO AS TO MAKE THE MAINTENANCE OPERATIONS POSSIBLE;
• POSITIONED SO THAT THEY CANNOT BE OBSTRUCTED;
• ANY EXTRACTOR HOODS IN THE ROOM WHERE THE DEVICE IS INSTALLED MUST NOT OPERATE AT THE SAME TIME as this could cause
smoke to enter the room, even with the replaces door closed.
The clean and non-contaminated air ow can also be obtained from a room adjacent to that of installation (indirect aeration and ventilation),
as long as the ow takes place freely through permanent openings communicating with the outside.
THE ADJACENT ROOM CANNOT BE USED AS A GARAGE, OR TO STORE COMBUSTIBLE MATERIAL OR FOR ANY OTHER ACTIVITY WITH A FIRE
HAZARD, BATHROOM, BEDROOM OR COMMON ROOM OF THE BUILDING.
Ventilation is deemed sucient when the room is equipped with air inlets according to the table:
Appliancecategories Referencestandard
Percentageofthe
netopeningsectionwithrespectto
theappliancefumesoutletsection
Minimumnetopeningvalueof
theventilationduct
Fireplaces UNI EN 13229 50% 200 cm²
Stoves UNI EN 13240 50% 100 cm²
Cookers UNI EN 12815 50% 100 cm²
INSTALLATION IN PREMISES WITH FIRE HAZARDS IS FORBIDDEN. INSTALLATION IN RESIDENTIAL PREMISES IN WHICH, IN ANY
CASE, THE DEPRESSION MEASURED DURING INSTALLATION BETWEEN THE INTERNAL AND EXTERNAL ENVIRONMENT IS GREATER
THAN 4 PA - REFERENCE FOR ITALY ACCORDING TO STANDARD UNI10683.
ALL NATIONAL, REGIONAL, PROVINCIAL AND MUNICIPAL LAWS AND STANDARDS IN FORCE IN THE COUNTRY WHERE THE APPLIANCE IS
INSTALLED MUST BE COMPLIED WITH.
30
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for La Nordica ROSETTA 5.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of La Nordica ROSETTA 5.0 in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 13.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of La Nordica ROSETTA 5.0

La Nordica ROSETTA 5.0 User Manual - Dutch - 32 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info