SPECIAL INFORMATION FOR THE BOILER’S USER AND INSTALLER
Boiler measurement (if applicable by current regulations)
It is recommended for the systems installer (heating installer) to be present when measuring the chimney sweep. If system problems are
encountered, the installer can intervene immediately in total safety. The measuring sequence must be strictly complied with!
Preparation:
- totally clean boiler (important: heat exchanger pipes)
- totally clean gas discharge pipe
- integrated and set draught controller (15 Pa)
- logs of combustion wood (50 cm long and approximate Ø of 8-10 cm)
- residual log humidity 12 % –20 % (measured in the centre)
- sucient capacity (temperature) in the Puer
- inspection of door gaskets (no inltration air must penetrate inside the boiler)
Boiler measurement:
- before measuring, the boiler must have been operating continuously for approximately 1 hour so that the ceramic parts reach the
operating temperature
- when starting to measure, the water temperature in the boiler must be minimum 60 °C
- the buer tank must be large enough to ensure constant heat reduction (the fan must operate with 100% of the total load)
- in the event of high fan power uctuations, you must stop the boiler’s measurement and nd the cause of irregular fan operation
Residual embers from previous combustion must be distributed evenly in the upper combustion chamber. A 4-5 cm bed of embers would be
ideal.
The sealed fuel must be piled above.
The upper loading door is then closed. For combustion, the ignition door is opened briey so that the gas discharge temperature reaches
approximately 200°C.
Measurement of the chimney sweep can be started 5 minutes after the ignition door is closed.
HEATING VALUES
SMOKE probe PT 1000
WATER probe KTY81-210
PUFFER probe KTY81-210
44
44


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for La Nordica LNK40 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of La Nordica LNK40 in the language / languages: English, German, French, Italian as an attachment in your email.

The manual is 17,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info