6. CONNECTION TO THE CHIMNEY
For safety reasons the door of the appliances with constructive system 1, must be opened only for the loading of the
fuel or for removing the ashes, while during the operation and the rest, the door of the hearth must remain closed.
The appliances with constructive system 2 must be connected to their own flue. The operating with open door is
allowed under supervision.
The stove is endowed with an upper exhaust pipe. The connection pipe to the flue must be the shortest possible,
right, tight and according to the current regulations.
The connection to the chimney must be performed with stable and strong pipes (we recommend a thickness of 2
mm). The pipe for smokes exhaust must be fixed hermetically to the chimney. The diameter inside the connection
pipe must correspond to the external diameter of the smokes exhaust small trunk of the stove. This is ensured by
pipes according to DIN 1298.
ATTENTION: Eventual flammable pieces in the area of 20 cm round the connection pipes must be changed
with fireproof and not sensitive to heat materials.
For a good operation of the equipment it is essential that in the installation place it is introduced sufficient air for
combustion (see chapt. 7).
The depression on the chimney should be 14 Pa (=1.4 mm of water column). The measurement must be done always
with the equipment hot (rating calorific value). When the depression exceeds 17 PA (1.7mm of water column) it is
necessary to reduce the same with the installation of an additional flue adjuster (butterfly valve) on the exhaust pipe
or in the chimney.
For safety reasons the door of the stove must be opened only for the loading of the fuel or for removing the ashes,
while during the operation and the rest, the door of the hearth must remain closed.
During its operation we suggest you slowly rotate the stove CARILLON. The rose window of the flue must be
fixed with nails or screws and the junction pipe must be fixed with a 90°bend, in order to avoid durin g the
rotation of the stove the detachment of the smoke pipe and a consequent danger of fire.
Picture 7
CHIMNEY CAPS - DISTANCES AND POSITIONING UNI 10683/98
Inclination of the roof
Distance between the roof ridge
and the stack
Minimum height of the stack (measured from the
outlet)
α
αα
α
A (m) H (m)
15°
< 1,85 m 0,50 m above the roof ridge
> 1,85 m 1,00 m from the roof
30°
< 1,50 m 0,50 m above the roof ridge
> 1,50 m 1,30 m from the roof
45°
< 1,30 m 0,50 m above the roof ridge
> 1,30 m 2,00 m from the roof
60°
< 1,20 m 0,50 m above the roof ridge
> 1,20 m 2,60 m from the roof
>
_
A
>A
0,5 m
H min.
α
(2)roof
(1)ridge axis
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for La Nordica CARILLON at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of La Nordica CARILLON in the language / languages: English, German, French, Italian as an attachment in your email.

The manual is 1,66 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info