22
Alarm AL1
Operating data lost due to fault in the
mains power supply.
Switch power off. Switch back on.
Alarm AS1 Faulty air temperature gauge Replace the temperature gauge
Alarm AS2 Faulty core probe Replace the probe
d-c alarm Top panel closed during cycle Open the top panel
Compressor not working
1-Clixon tripped because of an overload.
2-No power
3-Safety pressure switch tripped
1-Call a service technician
2-Check that the equipment is connected to
the power line
3-Call a service technician
Fans not turning
1-No power
2-Fan faulty
3-Condenser faulty
1-Check connection to mains power supply
2-Call a service technician to replace the fan
3-Call a service technician to replace the
condenser
The circuit board does not turn
on
1-No power
2-Protection fuse broken
1-Check connection to mains power supply
2-Call a service technician to replace the
board
The compressor is working but
the chamber is not cold
1-No cooling gas
2-Air condenser dirty
1-Call a service technician
2-Clean the condenser
Alarms
Technical specifications
Voltage
230 V-1-50Hz 230 V-1-60Hz 115 V-1-60Hz
Yield of blast chilling cycle 7 kg
Yield of shock freezing cycle 4 kg
Total number of wire shelves n°3
Total power 900 W 1000 W 1000 W
Input 3,9 A 4,6 A 8,8 A
Power cable 1.5m long with 16A shuko plug
Compressor power 410 (0,5) W (Hp)
Cooling gas type - quantity R404A - 850gr
Climatic class N
Net weight 45 kg
Standard features
2 stainless steel wire shelves (444x340x7 mm)
1 core probe
Left-hinged door