ERROR
CODE
MALFUNCTION
OR PROTECTION
FAILURE CAUSE
AND CORRECTIVE ACTION
Zone 2 water flow temp. sensor
(Tw2) fault.
1.Check the resistance of the sensor.
2. The Tw2 sensor connector is loosen. Reconnect it.
3.The Tw2 sensor connector is wet or there is water in.
remove the water, make the connector dry. Add waterproof adhesive
4. The Tw2 sensor failure, change a new sensor.
The plate heat exchanger
water outlet temperature
sensor (Tw_out) fault.
1.Check the resistance of the sensor.
2. The TW_out sensor connector is loosen. Reconnect it.
3.The TW_out sensor connector is wet or there is water in.
remove the water, make the connector dry. Add waterproof adhesive
4. The TW_out sensor failure, change a new sensor.
Three times “PP” protection
and Tw_out7
The same to "PP".
Communication fault between
master unit and slave unit
(in parallel)
1. Address code missing or address code setting duplicate, reset
address code;
2. The connected wire is wrong, reconnect the wire;
3. Chick whether the main board fuse is damaged;
4. Add a network matching wire betewwn the ports H1 and H2 at
the terminal of the communication system;
5. Put the SW9 to “on” of the master unit
Communication fault between
main control board of hydrautic
module and Ta / room
thermostart transfer PCB.
1. temperature collecting plate is set effectively, but it is notconnected
with temperature collecting plate.
2. temperature collecting plate connection wire is not connected,
check the connection line and joint
3. Temperature plate damaged, replace it
Inverter module board EE
PROM fault
1. The EEprom parameter is error, rewrite the EEprom data.
2. EEprom chip part is broken, change a new EEprom chip part.
3. Main PCB is broken, change a new PCB.
H6 displayed 10 times in 120
minutes.
Refer to H6
Low pressure protection
Pe<0.6 occured 3 times
in 1 hour in cooling mode
Refer to P0
Low pressure protection
1. System is lack of refrigerant volume. Charge the refrigerant in right
volume.
2.When at heating mode or heat water mode, Heat exchanger is dirty
or something is block on the surface. Clean the heat exchanger or
remove the obstruction.
3. The water flow is low in cooling mode.
4. Electrical expansion valve locked or winding connector is loosen.
Tap-tap the valve body and plug in/ plug off the connector for several
times to make sure the valve is working correctly. And install the
winding in the right location.
69


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info