55
3.1 HEAT MODE Enable or disable the heating mode 1 0 1 1 /
3.2 t_T4_FRESH_H The refresh time of climate related curves for heating
mode 0.5 0.5 6 0.5 hours
3.3 T4HMAX The maximum ambient operating temperature for heating
mode 25 20 35 1
3.4 T4HMIN The minimum ambient operating temperature for heating
mode -15 -25 30 1
3.5 dT1SH The temperature difference for starting the unit (T1) 5 2 20 1
3.6 dTSH The temperature difference for starting the unit (Ta) 2 1 10 1
3.8 T1SetH1 The setting temperature 1 of climate related curves for
heating mode 35 25 65 1
3.9 T1SetH2 The setting temperature 2 of climate related curves for
heating mode 28 25 65 1
3.10 T4H1 The ambient temperature 1 of climate related curves for
heating mode -5 -25 35 1
3.11 T4H2 The ambient temperature 2 of climate related curves for
heating mode 7 -25 35 1
3.12 ZONE1 H-EMISSION The type of zone1 end for heating mode0=FCU(fan coil
unit)1=RAD.(radiator)2=FLH(floor heating) 1 0 2 1 /
3.13 ZONE2 H-EMISSION The type of zone2 end for heating mode0=FCU(fan coil
unit)1=RAD.(radiator)2=FLH(floor heating) 2 0 2 1 /
3.14 t_DELAY_PUMP the time that the compressor has run before starting the
pump. 2 0.5 20 0.5 MIN
4.1 T4AUTOCMIN The minimum operating ambient temperature for cooling in
auto mode 25 20 29 1
4.2 T4AUTOHMAX The maximum operating ambient temperature for heating
in auto mode 17 10 17 1
5.1 WATER FLOW TEMP. Enable or disable the WATER FLOW TEMP.:0=NON,1=YES 1 0 1 1 /
5.2 ROOM TEMP. Enable or disable the ROOM TEMP.:0=NON,1=YES 0 0 1 1 /
5.3 DOUBLE ZONE Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES 0 0 1 1 /
7.1 dT1_IBH_ON The temperature difference betw een T1S and T1 for
starting the backup heater. 5 2 10 1
7.2 t_IBH_DELAY The time that the compressor has run before the first
backup heater turns on 30 15 120 5 MIN
7.3 T4_IBH_ON The ambient temperature for starting the backup heater -5 -15 30 1
7.7 IBH_LOCATE
IBH/AHS installation location PIPE LOOP=0; BUFFER TANK=1
0 0 0 0
7.8 P_IBH1
Power input of IBH1
0 0 20 0.5 kW
7.9 P_IBH2
Power input of IBH2
0 0 20 0.5 kW
7.10 P_TBH
Power input of TBH
2 0 20 0.5 kW
7.4 dT1_AHS_ON The temperature difference betw een T1S and T1B for
turning the additional heating source on 5 2 20 1
7.5 t_AHS_DELAY The time that the compressor has run before starting the
additional heating source 30 5 120 5 MIN
7.6 T4_AHS_ON The ambient temperature for starting the additional
heating source -5 -15 30 1
8.1 T1S_H.A_H The target outlet w ater temperature for space heating
w hen in holiday aw ay mode 25 20 25 1
8.2 T5S_H.A_DHW The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode 25 20 25 1
12.1 PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first
preheating for floor 25 25 35 1
12.3 t_FIRSTFH The time last for preheating floor 72 48 96 12 HOUR
The style of room thermostat
0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
6.1 ROOM THERMOSTAT 0 0 3 1 /
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info