NOTE
The volume of balance tank(8) should be greater than 40L. The drain valve (6) should be installed at the lowest
positon of the system.
As the temperature sensor attached in the user interface is used to detect the room temperature, the user interface
(4) should be placed in the room where floor heating loops and fan coil units is installed and away from the heating
source. Correct configuration should be applied in the user interface (refer to 10.7 field settings/TEMP. TYPE
SETTING). The first setpoint is water temperature which can be set on the main page of user interface, the second
setpoint is calculated from climate related curves, the target outlet water temperature is the higher one of these two
setpoints. The unit will turn off when the room temperature reaches the target temperature.
Pump operation and space heating
The pump (1.7) and (10) will operate when there is request for heating from A and / or B. Pump (23.1) will operate when the
room temperature of zone B is lower than the set point which set in the user interface. The outdoor unit will start operating to
achieve the target water flow temperature.
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
2
3
Assembly unit Assembly unit
Coding Coding
FHL 1…n
4
6
Outdoor unit
Manometer
Pressure relief valve
Expansion vessel
Plate heat exchanger
Air purge valve
Flow switch
P_i: Circulation pump in the unit
Y-shape filter
Stop valve (field supply)
Wired controller
Drain valve (field supply)
7
8
8.1
8.2
9
10
11
17
23
23.1
Fill valve (field supply)
Balance tank (field supply)
Air purge valve
Drain valve
Expansion vessel (field supply)
P_o: Outside circulation pump (field supply)
Collector / distributor (field supply)
Floor heating loop (field supply)
5B Room thermostat for zone 2 (field supply)
Bypass valve (field supply)
Mixing station (field supply)
P_c: zone 2 pump (field supply)
FCU 1...n Fan coil units (field supply)
23.2 SV3: 3-way valve (field supply)
24 Tw2: Zone 2 water flow temp. (individual purchase)
5A Room thermostat for zone 1 (field supply)
23
6 7
8.1
8.2
8
10
9
11
11
FHL1 FHL2 FHLn
FCUnFCU2FCU1
17
4
23.1
23
23.2
24
A
B
1
1.5
1.4
1.2
1.3
1.7
1.6
1.1
The operation and configuration of the field water circuit is the responsibility of the installer.
We only offer a dual set point control function. This function allows two set points to be generated. Depending on the
required water temperature (floor heating loops and/or fan coil units are required) the first set point or second set point can
be activated. See 10.7 field setting /TEMP. TYPE SETTING.
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info