Main Menu Buttons - Settings
Installation Settings
(Continued)
Heat Pump Settings
Aux Heat Lockout Temp
(65˚)
HP Lockout Outdoor Temp
(65˚)
Heat Pump will not run below this temp. (0˚ - 75˚ F)
Aux Heat will not run above this temp. (0˚ - 75˚ F) GAS/EL or HP dip
switch must be set for HP and GAS or ELEC dip switch must be set for ELEC.
Aux Heat Lockout - DISABLED
Aux Heat Lockout - ENABLED
Turns on Aux Heat Lockout.
Heat Pump Lockout - DISABLED
Heat Pump Lockout - ENABLED
Turns on Heat Pump Lockout.
(Only available
when dip switch
is set for Heat
Pump operation.)
AUX Output Settings
AUX output usage
(W3)
Allows the W3/AUX output to be used for Heating, Humidification, or
Dehumidification.
IMPORTANT: Aux Output Usage must be set for Hum or Dehum
before any settings will take effect in the Humidity Main Menu.
AUX output polarity
(NO)
The AUX Output polarity may be set for
Normally Open or Normally Closed to
accommodate different types of
humidification and dehumidification
equipment.
A local outdoor
sensor connected
to the thermostat
is required.
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Johnson Control T8690 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Johnson Control T8690 in the language / languages: English as an attachment in your email.

The manual is 8,17 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info