T600MSx-3 Multi-Stage Thermostat Installation Instructions6
Lockout Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Function Lockout Level
(0) (1) (2)
Occupancy
Override
Access Access No Access
Permanent
Temperature
Setpoints
Access No Access No Access
Temporary
Temperature
Setpoints
Access Access No Access
System Mode
Setting
Access No Access No Access
Fan Mode Setting Access No Access No Access
Schedule
Setting
4
Access No Access No Access
Clock Setting
4
Access Access Access
Permanent Hold
4
Access No Access No Access
Pwr del
2
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Range: 10.0 to 120.0 sec
Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat.
Default: off
(on): Enabled
(off): Disabled
Heat max
3
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Cool min
3
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Anticycl Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Heat cph Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Range: 3.0 to 8.0 cycles per hour
Cool cph Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Range: 3.0 or 4.0 cycles per hour
Table 2: Installer Configuration Menu (Part 2 of 4)
Parameter
Appearing
on Display
Description and Default Selection Options
6


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Johnson Control T600MSP-3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Johnson Control T600MSP-3 in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info