T600MEP-3 Multi-stage Economizer Thermostat Installation Instructions8
H stage Reverts the operation of a two-stage
thermostat to a single-stage
thermostat when the second heating
stage is not needed.
Default: 2.0
(1.0): One Stage
(2.0): Two Stages
C stage Reverts the operation of a two-stage
thermostat to a single-stage
thermostat when the second cooling
stage is not needed.
Default: 2.0
(1.0): One Stage
(2.0): Two Stages
H lock Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
C lock Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
2/4event Sets the number of events within a
24-hour period.
Default: 4.0
(2.0): Two events (one occupied and one unoccupied) within a
24-hour period
(4.0): Four events (two occupied and two unoccupied) within a
24-hour period
Aux cont Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
(n.c.): Contact open = Occupied; contact closed = Unoccupied
(n.o.): Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied
schedule (or the NSB contact on one of the digital inputs, if used).
Prog rec Provides the desired occupied
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Default: off
(on): Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off): Disabled (provides the desired occupied temperature after the
occupied schedule begins)
Chngstpt
3
Sets the economizer changeover
strategy, based on the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
When the OA temperature is below
the changeover setpoint, free
cooling is used (economizer
operation). When the OA
temperature is above the setpoint,
mechanical cooling is used
(compressor operation).
Default: 55.0°F/13.0°C
Range: 14.0°F/-10.0°C to 70.0°F/21.0°C
Table 2: Installer Configuration Menu (Part 4 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Johnson Control T600MEP-3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Johnson Control T600MEP-3 in the language / languages: English as an attachment in your email.

The manual is 0,26 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info