37748
15
Zoom out
Zoom in
Previous page
1/17
Next page
T600HPx-3 Heat Pump Thermostats Installation Instructions 1
Applications
The T600HPN-3 non-programmable and T600HPP-3
programmable thermostats are specifically designed
for control of heat pump commercial heating and
cooling equipment.
North American Emissions Compliance
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference,
in which case the user will be required to correct the
interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the T600HPx-3 thermostat:
on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
Note: Allow for vertical air circulation to the
T600HPx-3 thermostat.
To install the thermostat:
1. Use a Phillips-head screwdriver to remove the
security screw on the bottom of the thermostat
cover.
2. Pull the bottom edge of the thermostat cover and
open the thermostat as illustrated in Figure 1.
IMPORTANT: The T600HPx-3 Thermostat is
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat could lead to personal
injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices such as
supervisory or alarm systems or safety or limit
controls intended to warn of or protect against failure
or malfunction of the thermostat.
Figure 1: Removing the Thermostat Cover
F
I
G
:
c
v
r
_
r
m
v
l
T600HPx-3 Heat Pump Thermostats
Installation Instructions
T600HPN-3, T600HPP-3
Part No. 24-9890-595, Rev. —
Issued September 20, 2006
T600HPx-3 Heat Pump Thermostats Installation Instructions2
3. Carefully pull the locking tabs on the right side of
the thermostat mounting base and unlock the
Printed Circuit Board (PCB). Open the PCB to the
left as illustrated in Figure 2.
4. Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the hole in the
thermostat mounting base.
5. Align the thermostat mounting base on the wall and
use the base as a template to mark the two
mounting hole locations.
Note: Be sure to position the thermostat mounting
base so that the arrow on the base points upward
to indicate the top of the thermostat.
6. Drill a 3/16 in. (5 mm) hole at each of the two
marked locations and tap nylon anchors (included
with the thermostat) flush to the wall surface.
7. Position the thermostat mounting base on the wall
and use the two mounting screws (included with
the thermostat) to secure the base to the surface
as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting
screws.
8. Swing the PCB back to the right and carefully snap
it into the locking tabs on the thermostat mounting
base.
9. Pull the pull-tabs on each of the connectors and
remove the screw terminal blocks as illustrated in
Figure 4.
Wiring
When an existing thermostat is replaced, remove and
label the wires to identify the terminal functions. When
a T600HPx-3 thermostat is replaced, simply remove
the old screw terminal blocks and reinsert them onto
the PCB of the replacement thermostat.
Figure 2: Opening the Thermostat PCB
FIG:prntd_crct_brd
PCB
Locking
Tabs
Figure 3: Securing the Thermostat
Mounting Base to the Wall
FIG:mntng_bs
!
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the T600HPx-3 thermostat.
Figure 4: Removing the Screw Terminal Blocks
F
I
G
:
t
r
m
n
l
_
b
l
c
k
s
T600HPx-3 Heat Pump Thermostats Installation Instructions 3
To wire the thermostat:
1. Strip the ends of each wire a 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
2. Carefully push any excess wire back into the wall.
Seal the hole in the wall with fireproof material to
prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the thermostat cover to the mounting
base (top side first).
Note: Use a Phillips-head screwdriver to reinstall
the security screw on the bottom of the thermostat
cover.
Figure 5: Terminal Blocks
Y2
Y1 G RC
C
RH W1 O/B
Aux D1 D2 RS
Scom
OS
MS
5 pole left top connector
3 pole right top connector
7 pole bottom connector
F
I
G
:
T
6
0
0
H
P
x
-
3
_
t
r
m
b
l
k
1
2
3
45
6
7
8
10 11 1
2
13
14
1
5
16
Figure 6: Wiring the T600HPx-3 Thermostats
AUX
D1
D2
Scom
OS
RS
If using the same power source
for the thermostat and heating
loads, install a jumper
across RC and RH.
Remote
Room
Sensor
Remote
Outdoor
Sensor
24 VAC
Thermostat Power
Aux
Heat
Y2 Y1
GRCC
RH W1 O/B
Aux
Fan
Comp 2
Comp 1
Rev
Valve
F
I
G
:
T
6
0
0
H
P
x
-
3
_
w
r
n
g
Isolated Contact
- Lighting
- On/Off Actuation
- Exhaust Fan
Table 1: Terminal Identification (See Figure 5.)
Number Label Function
1Y2Energizes second-stage compressor
on a call for heating or cooling.
2Y1Energizes first-stage compressor on
a call for heating or cooling.
3GEnergizes fan in accordance with
selected fan mode.
4RC24 VAC from equipment transformer
5C24 VAC (Common) from equipment
transformer
6RH24 VAC for auxiliary heating.
7W1Energizes on a call for auxiliary
heating.
8 O/B Reversing valve. Configurable to
energize a valve on a call for heating
or a call for cooling.
10 Aux Auxiliary output
11 DI1 Configurable Digital Input 1
12 DI2 Configurable Digital Input 2
13 RS Remote Room Temperature Sensor
14 Scom Sensor Common
15 OS Outdoor Air Sensor
16 MS Not Used
T600HPx-3 Heat Pump Thermostats Installation Instructions4
Setup and Adjustments
Thermostat Operation Overview
Thermostat User Interface Keys
The T600HPx-3 thermostat user interface consists of
five keys on the front cover (as illustrated in Figure 8).
The function of each key is as follows:
•Use the YES/SCROLL key to:
- confirm menu selections and to advance to the
next menu item
- stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu
Note: When the thermostat is left unattended for
45 seconds, the thermostat display resumes
scrolling.
•Use the NO key to decline a parameter change and
to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or exit the menu
- access the Installer Configuration Menu or to
exit the menu (See the Configuring the
T600HPx-3 Thermostat section.)
•Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
Backlit Liquid Crystal Display (LCD)
The T600HPx-3 thermostat includes a 2-line,
8-character backlit display. Low-level backlighting is
present during normal operation, and it brightens when
any user interface key is pressed. The backlight returns
to low level when the thermostat is left unattended for
45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The FAN LED is on when the fan is on.
•The AUX HEAT LED is on when auxiliary heat is
on
•The HEAT-PUMP LED is on when the heat-pump
compressor is on.
Separate 24 VAC
Transformer
Y2 Y1
GRCC
RH
W1
O/B
R4
To Auxiliary
Heat Circuit
O/B
RC
G
Y1 Y2
Heat Pump Circuit Card
R4-1
R1-1 R2-1
R3-1
R3
R1
R2
Note:
Use 24 VAC interface relays
(provided by the user).
F
I
G
:
T
6
0
0
H
P
x
-
3
_
V
D
C
Figure 7: Wiring the T600HPx-3 Thermostat for VDC Applications
Figure 8: Front Cover of Thermostat
70.0ºF
Room Temp
Y
ES NO
Backlit, plain text
LCD is easy to read
in any condition.
Five keys on the thermostat
make operation easy and intuitive.
LEDs indicate
system activity.
F
I
G
:
T
6
0
0
_
f
r
n
t
T600HPx-3 Heat Pump Thermostats Installation Instructions 5
Programming Overview
There are three menus used to view, program, and
configure the T600HPx-3 thermostat:
The Status Display Menu is displayed during normal
thermostat operation. This menu continuously scrolls
through the following parameters:
Room Temperature
Day and Time (T600HPP-3)
System Mode
Occupancy Status – Occupied/Unoccupied/
Override
Outdoor Temperature – An outdoor air temperature
sensor must be connected.
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: Press the YES/SCROLL key to temporarily stop
this menu from scrolling.
The Main User Menu is used to access and change
the basic operating parameters of the thermostat.
Access this menu by pressing the MENU key during
normal thermostat operation.
The Installer Configuration Menu is used to set up
the thermostat for application-specific operation. To
access this menu, press and hold the MENU key for
approximately 8 seconds.
Configuring the T600HPx-3 Thermostat
The T600HPx-3 thermostat comes from the factory
with default settings for all configurable parameters.
The default settings are shown in Table 2. To
reconfigure the parameters via the thermostat, follow
the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the MENU key for approximately 8
seconds.
2. Once the Installer Configuration Menu begins,
press the NO key to scroll through the parameters
listed in Table 2.
3. When the desired parameter is displayed, use the
YES key to choose the desired selection option.
4. Press the YES key and then the NO key to
continue scrolling through the parameters.
To exit the Installer Configuration Menu any time, press
the MENU key, and at the exit prompt, press the YES
key. To pass over a parameter without changing it,
press the NO key.
When the thermostat is in the Installer Configuration
Menu and left unattended for approximately 8 seconds,
the thermostat reverts to the Status Display Menu.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
Each input can be configured to the Selection Options
included in Table 2.
Table 2: Installer Configuration Menu (Part 1 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
DI1
1
Configuration of Digital Input 1.
Default: None
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
T600HPx-3 Heat Pump Thermostats Installation Instructions6
DI2
1
Configuration of Digital Input 2.
Default: None
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the thermostat when the
input is energized. This input can be tied into the air conditioning unit
control card, which provides an alarm should there be a malfunction.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
Lockout Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Function Lockout Level
(0) (1) (2)
Occupancy Override Access Access No Access
Permanent
Temperature
Setpoints
Access No Access No Access
Temporary
Temperature
Setpoints
Access Access No Access
System Mode Setting Access No Access No Access
Fan Mode Setting Access No Access No Access
Schedule Setting
5
Access No Access No Access
Clock Setting
5
Access Access Access
Permanent Hold
5
Access No Access No Access
Pwr del
2
Sets the delay time period at
thermostat power up, or at each
time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
Range: 10.0 to 120.0 sec
Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the thermostat. Forces system to
Emergency Mode.
Default: off
(on): Enabled
(off): Disabled
Heat max
3
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Cool min
3
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.0°C
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
Table 2: Installer Configuration Menu (Part 2 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
T600HPx-3 Heat Pump Thermostats Installation Instructions 7
Anticycl Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Heat cph Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Range: 3.0 to 8.0 cycles per hour
Cool cph Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Range: 3.0 or 4.0 cycles per hour
Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
Fan cont Determines how the fan is activated
in response to Emergency Heat
mode. Fan cont applies to W1
(auxiliary heat) and Fan Mode auto
only. Fan cont does not affect fan
operation on a call for cooling or
heating to the compressor (Y1 and
Y2).
Default: on
(off): The thermostat will not activate the fan in response to a call
for Emergency Heat. The fan is activated by the equipment fan and
limit control.
(on): Enables the thermostat to activate the fan in response to a call
for heating or cooling.
Fan del Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default: 3.0 hrs
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Cal OS Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
T600HPx-3 Heat Pump Thermostats Installation Instructions8
HP stage Sets the number of heat pump
compressor stages.
Default: 2.0
(1.0): One Stage
(2.0): Two Stages
Reverts the operation of a two-stage thermostat to a single-stage
thermostat when the second cooling stage is not needed.
H lock
4
Discontinues heating operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: 120°F/49°C
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
C lock
4
Discontinues cooling operation in
response to the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
Default: -40°F/-40°C
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
2/4event
5
Sets the number of events within a
24-hour period.
Default: 2.0
(2.0): Two events (one occupied and one unoccupied) within a
24-hour period
(4.0): Four events (two occupied and two unoccupied) within a
24-hour period
Aux cont Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
(n.c.): Contact open = Occupied; contact closed = Unoccupied
(n.o.): Contact closed = Occupied; contact open = Unoccupied
The contact toggles with the internal Occupied/Unoccupied schedule
(or the NSB contact on one of the digital inputs, if used).
Prog rec
5
Provides the desired occupied
temperature either at the start of the
occupied schedule or after the
occupied schedule begins.
Note: Progressive recovery is
disabled if either DI1 or DI2
is configured as remote
NSB.
Default: off
(on): Enabled (provides the desired occupied temperature at the
start of the occupied schedule)
(off): Disabled (provides the desired occupied temperature after the
occupied schedule begins)
Hi b. p.
4
Sets the high balance point – the
outdoor air temperature at which the
auxiliary heat is not used.
Default: 90.0°F/32.0°C
Range: 34.0°F/1.0°C to 90.0°F/32.0°C
Above the high balance point, only the heat pump is used to
maintain the heating setpoint. If no outdoor air sensor is connected
to Terminal OS, auxiliary heat pump operation may still be used
above the high balance point.
Lo b. p.
4
Sets the low balance point – the
outdoor air temperature at which the
heat pump operation terminates
when the heat pump is in the
heating mode.
Default: -12.0°F/-24.0°C
Range: -40.0°F/-40°C to 30.0°F/-1.0°C
Below the low balance point, only the auxiliary heat is used to
maintain the heating setpoint. Heat pump operation may still be used
below the low balance point if no outdoor air sensor is connected to
Terminal OS.
Table 2: Installer Configuration Menu (Part 4 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
T600HPx-3 Heat Pump Thermostats Installation Instructions 9
Comf/eco Selects how the auxiliary heat is
used.
Default: comfort
(economy) – in the heating mode: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized to satisfy
the setpoint only when the temperature has dropped 2F°/1C° below
the heating setpoint.
Note: Selecting economy in the heating mode adds a deadband
between the heat pump and auxiliary heat. The actual
temperature maintained is lower than the true heating
setpoint to maximize the heat pump operation. When the
outdoor air temperature drops below the low balance point,
the deadband is eliminated.
(economy) – in the emergency heat mode: The setpoint that is
maintained is the heating setpoint.
(comfort) – in the heating mode: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized to satisfy
the setpoint.
Re valve Governs the reversing valve
operation.
Default: O
(B): Energizes the valve in heating operation (valve is normally cool)
(O): Energizes the valve in cooling operation (valve is normally heat)
Comp/aux Sets the mode of interaction
between the heat pump and the
auxiliary heat.
Default: off
(on) – in the heating mode only: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized and the
heat pump is shut off. This typically applies when the air handler
heat pump coil is installed after the auxiliary heat. There is a
2-minute delay to restart the heat pump after the auxiliary heat is
shut down.
(off) – in the heating mode only: If the heat pump is not able to
satisfy the heating setpoint, the auxiliary heat is energized at the
same time as the heat pump stage. This typically applies when the
air handler heat pump coil is installed before the auxiliary heat (all
electric systems).
1. Setting DI1 or DI2 to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables
schedules and the Schedule menu. (T600HPP-3 only)
2. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and
hold the UP or DOWN arrow key to change the numeric value in increments of ten.
3. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press
and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
4. When the outdoor air sensor is not connected or it has a short, the thermostat bypasses heating lockout, cooling lockout,
high balance point, and low balance point. Emergency mode bypasses heating lockout and permits auxiliary heating
whenever a heating demand occurs.
5. T600HPP-3 only
Table 2: Installer Configuration Menu (Part 5 of 5)
Parameter
Appearing
on Display
Description and Default Selection Options
T600HPx-3 Heat Pump Thermostats Installation Instructions10
Operation
Programming/Operating the T600HPx-3
Thermostat
Once the thermostat is configured via the Installer
Configuration Menu, its operating parameters can be
programmed via the Main User Menu. Access this
menu by pressing the MENU key during normal
thermostat operation. The Main User Menu contains
the basic operating features of the thermostat.
The Main User Menu also uses Auto Help, which is
displayed automatically in the menu when there is a
pause in programming activity. To exit Auto Help,
continue with the programming selection. When the
thermostat is in the Main User Menu and is left
unattended for 45 seconds, the menu reverts to the
Status Display Menu.
SeeTable 3 to program the thermostat.
Note: Schedule Set and Clock Set are available only
on T600HPP-3 models.
Enabling Temporary Override Schedule
Note: The Override Schedule function is available in
T600HPN-3 models only when DI1 or DI2 is configured
as remote NSB.
Note: The Override Schedule prompt only appears
when in the Unoccupied (Unoccup) or Unoccupied
Hold (Unoccup hold) Mode.
The override schedule prompt only appears when the
thermostat is in the unoccupied state. This menu
selection gives the user the option of overriding the
unoccupied setpoints with the occupied setpoints for
the amount of time specified under the TOccTime
parameter. See the Configuring the T600HPx-3
Thermostat section.
Note: If DI1 or DI2 is configured to operate as a
remote override contact, this menu is disabled.
To override the unoccupied state while in the Main User
Menu:
1. Press the NO key to all prompts until the Override
Schedule prompt appears. If the thermostat is in
the unoccupied state, this is the first prompt.
2. Press the YES key to enable the temporary
override. The thermostat returns to the Status
Display Menu.
When scrolling through the Status Display Menu,
Override now appears for the schedule status
parameter.
Table 3: Programming the T600HPx-3 Thermostat
(Part 1 of 2)
Thermostat
Display
Description
Press the MENU key while in the
Status Display Menu to enter the
Main User Menu.
Overrides Unoccupied Setpoints
Only Appears if Thermostat is in
Unoccupied State
See the Enabling Temporary
Override Schedule section.
Cancels Override mode.
Sets the Temperature Setpoints
See the Entering Permanent
Temperature Setpoints section.
Selects the System Mode Default:
Automatic (auto)
See the Selecting the System Mode
section.
Selects the Fan Mode Default:
Automatic (auto) for T600HPN-3
Smart (smart) for T600HPP-3
See the Selecting the Fan Mode
section.
RoomTemp
75.0
°
F
Override
schd Y/N
Cancel
ovrd Y/N
Temperat
set? Y/N
Sys mode
set? Y/N
Fan mode
set? Y/N
Sets the Occupied and Unoccupied
Time Periods
See the Programming the Daily
Schedule – Two-Event and
Programming the Daily Schedule –
Four-Event sections.
Sets the Day and Time
See the
Setting the Day and Time
section.
Sets a Permanent Hold on the
Schedule or Resumes the Schedule
See the
Setting Schedule Hold
section.
Table 3: Programming the T600HPx-3 Thermostat
(Part 2 of 2)
Thermostat
Display
Description
Schedule
set? Y/N
Clock
set? Y/N
Schedule
hold? Y/N
T600HPx-3 Heat Pump Thermostats Installation Instructions 15
Setting the Day and Time (T600HPP-3)
Upon initial power up (or after a power loss of greater
than 6 hours), the thermostat shows a SetClock alarm
on its display. As the thermostat scrolls through the
Status Display Menu, the SetClock message causes
the backlight to light up until the clock is set.
When changing the time, press the UP/DOWN arrow
keys once to change the time in 1-minute increments;
press and hold down the keys to change the time in
30-minute increments.
To set the clock while in the Main User Menu:
1. Press the NO key to all prompts until the clock set
prompt appears on the display. Press the YES key
to enter the clock set menu. Press the YES key to
set the time or press the NO key to advance to the
day set menu.
2. Press the UP/DOWN arrow keys to adjust the time.
When the correct time is displayed, press the YES
key to store the time.
3. Press the YES key to enter the day set menu or
press the NO key to enter the clock format menu.
4. Press the UP/DOWN arrow keys to adjust the day.
When the correct day is displayed, press the YES
key to store the day.
5. Press the YES key to choose the time format or
press the NO key to access the Main User Menu
exit prompt.
6. Press the UP/DOWN arrow keys to select the
desired time format. Press the YES key to enter
the format.
7. Press the YES key to return to the Status Display
Menu or press the NO key to return to the time set
menu.
When the thermostat scrolls through the day and time,
the new day and time should show on the display and
no alarm or backlight should be present. If the day or
time is incorrect, repeat the Setting the Day and Time
procedure.
Setting Schedule Hold
The schedule hold menu is used to set a permanent
hold on the internal scheduling or resume the
schedule. The permanent hold is typically used for
non-scheduled events that extend for long periods of
time.
Note: The Override Schedule function is available in
T600HPN-3 models only if DI1 or DI2 is configured for
remote NSB.
Note: The Schedule Hold menu is also displayed if
DI1 or DI2 is configured for remote NSB.
The following selections are available in the schedule
hold menu:
Permanent Occupied Hold (occ hold): This
selection puts the thermostat into a permanent
occupied state via the occupied setpoints.
Occupied hold appears in the Status Display Menu
when this selection is active.
Permanent Unoccupied Hold: This selection puts
the thermostat into a permanent unoccupied state
via the unoccupied setpoints. Unoccup hold
appears in the Status Display Menu when this
selection is active.
Table 7: Four-Event Office Schedule
Event 1 Event 2 Event 3 Event 4
Occupied Unoccupied Occupied 2 Unoccupied 2
Event Cool Heat Cool Heat Cool Heat Cool Heat
72°F
(22°C)
70°F
(21°C)
80°F
(27°C)
62°F
(17°C)
72°F
(22°C)
70°F
(21°C)
80°F
(27°C)
62°F
(17°C)
Monday 7:00 A.M. 5:00 P.M.
12:00 P.M.
1
12:00 P.M.
1
Tuesday 7:00 A.M. 5:00 P.M.
12:00 P.M.
1
12:00 P.M.
1
Wednesday 7:00 A.M. 5:00 P.M.
12:00 P.M.
1
12:00 P.M.
1
Thursday 7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M.
Friday 7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M.
Saturday
12:00 P.M.
1
12:00 P.M.
1
12:00 P.M.
1
12:00 P.M.
1
Sunday
12:00 P.M.
1
12:00 P.M.
1
12:00 P.M.
1
12:00 P.M.
1
1. Programming different events to the same time for that day cancels those events and leaves the thermostat in the
unoccupied state.
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Johnson Control T600HPP-3 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Johnson Control T600HPP-3 in the language / languages: English as an attachment in your email.

The manual is 0,26 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info