Refrigerant Piping
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool
clockwise until the pipe is fully flared. Flare
the pipe in accordance with the dimensions
shown in table 7.3.
Table 7.3: PIPING EXTENSION BEYOND FLARE
FORM
Pipe
gauge
Tightening
torque
Flare dimension (A)
(Unit: mm/Inch)
Flare shape
Min. Max .
Ø 6.4
R0.4~0.8
45 °±2
90 °
±4
A
Fig. 7.9
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1 65-67 N.m
(663-683 kgf.cm) 23.2/0.91 23.7/0.93
8. Remove the flaring tool and flare form,
then inspect the end of the pipe for cracks
and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first,
then connect it to the outdoor unit. You should
first connect the low-pressure pipe, then the high-
pressure pipe.
1. When connecting the flare nuts, apply a
thin coat of refrigeration oil to the flared
ends of the pipes.
2. Align the center of the two pipes that you
will connect.
Indoor unit tubing Flare nut Pipe
Fig. 7.10
3. Tighten the flare nut as tightly as possible
by hand.
4. Using a spanner, grip the nut on the unit
tubing.
5. While firmly gripping the nut, use a torque
wrench to tighten the flare nut according
to the torque values in table 7.3.
NOTE: Use both a spanner and a torque wrench
when connecting or disconnecting pipes to/from
the unit.
Fig. 7.11
CAUTION
Ensure to wrap insulation around the piping.
Direct contact with the bare piping may result
in burns or frostbite.
Make sure the pipe is properly connected.
Over tightening may damage the bell mouth
and under tightening may lead to leakage.
NOTE ON MINIMUM BEND RADIUS
Carefully bend the tubing in the middle
according to the diagram below. DO NOT bend
the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
min-radius 10cm (3.9”)
Fig. 7.12
6. After connecting the copper pipes to the
indoor unit, wrap the power cable, signal
cable and the piping together with
binding tape.
NOTE: DO NOT intertwine signal cable with
other wires. While bundling these items
together, do not intertwine or cross the signal
cable with any other wiring.
7. Thread this pipeline through the wall and
connect it to the outdoor unit.
8. Insulate all the piping, including the valves
of the outdoor unit.
9. Open the stop valves of the outdoor unit
to start the flow of the refrigerant between
the indoor and outdoor unit.
CAUTION
Check to make sure there is no refrigerant leak
after completing the installation work. If there is
a refrigerant leak, ventilate the area immediately
and evacuate the system (refer to the Air
Evacuation section of this manual).
Ø 22 75-85N.m
(765-867 kgf.cm) 26.4/1.04 26.9/1.06
18-20N.m
(183-204kgf.cm) 8.4/0.33 8.7/0.34
25-26 N.m
(255-265 kgf.cm) 13.2/0.52 13.5/0.53
35-36 N.m
(357-367 kgf.cm) 16.2/0.64 16.5/0.65
45-47 N.m
(459-480 kgf.cm) 19.2/0.76 19.7/0.78
Page 21
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board(PCB) is
designed with a fuse to provide overcurrent
protection. The specifications of the fuse are
printed on the circuit board, such as:
Indoor unit: T3.15A/250VAC, T5A/250VAC.
(applicable for unit adopts R32 refrigerant)
Outdoor unit: T20A/250VAC(for <24000Btu/h
unit), T30A/250VAC(for >24000Btu/h unit)
Wiring
Safety Precautions
WARNING
Be sure to disconnect the power supply
before working on the unit.
All electrical wiring must be done
according to local and national regulations.
Electrical wiring must be done by a
qualified technician. Improper connections
may cause electrical malfunction, injury
and fire.
An independent circuit and single outlet
must be used for this unit. DO NOT plug
another appliance or charger into the
same outlet.If the electrical circuit capacity
is not enough or there is a defect in the
electrical work, it can lead to shock, fire,
unit and property damage.
Connect the power cable to the terminals
and fasten it with a clamp. An insecure
connection may cause fire.
Make sure that all wiring is done correctly
and the control board cover is properly
installed. Failure to do so can cause
overheating at the connection points, fire,
and electrical shock.
Ensure that main supply connection is
made through a switch that disconnects
all poles, with contact gap of a least 3mm
(0.118”).
DO NOT modify the length of the power
cord or use an extension cord.
CAUTION
Connect the outdoor wires before
connecting the indoor wires.
Make sure you ground the unit. The
grounding wire should be away from gas
pipes, water pipes, lightning rods,
telephone or other grounding wires.
Improper grounding may cause electrical
shock.
DO NOT connect the unit with the power
source until all wiring and piping is
completed.
Make sure that you do not cross your
electrical wiring with your signal wiring, as
this can cause distortion and interference.
Follow these instructions to prevent distortion
when the compressor starts:
The unit must be connected to the main
outlet. Normally, the power supply must
have a low output impedance of 32 ohms.
No other equipment should be connected
to the same power circuit.
The unit’s power information can be found
on the rating sticker on the product.
Outdoor Unit Wiring
WARNING
Before performing any electrical or wiring work,
turn off the main power to the system.
1. Prepare the cable for connection
a. You must first choose the right cable size
before preparing it for connection. Be sure
to use H07RN-F cables.
Table 8.1: Minimum Cross-Sectional Area
of Power and Signal Cables North America
Rated Current of
Appliance (A) AWG
7 18
7 - 13 16
13 - 18 14
18 - 25 12
25 - 30 10
8
NOTE: The fuse is made of ceramic.
20


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Inventor U5MRT32 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Inventor U5MRT32 in the language / languages: English, German as an attachment in your email.

The manual is 23.57 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Inventor U5MRT32

Inventor U5MRT32 User Manual - English, German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info