51
05.2004 TR10A011 RE
ENGLISH
7 240 sec.
8 270 sec.
9 300 sec.
* = factory setting
Afterwards, switch to menu 0 by pressing the PRG button.
5.2 Service menus: menu 3 - menu 9
After the selection has been made, the menu number
is displayed for one second, after which the correspon-
ding menu parameter flashes up. To be able to alter this
parameter, the PRG button must be pressed for 3 se-
conds. As a result, the menu number is displayed once
again. After the 3 seconds have elapsed, the parameter
flashes up again. A new value can now be entered via
the OPEN and CLOSE buttons.
If the PRG button is released prematurely, the system
switches to the next menu. If within 60 seconds in the
tuned state no button is pressed, the system automa-
tically returns to normal operation (menu 0).
5.2.1 Setting the automatic closing timer (prerequisite is
the fitting of a photocell and/or closing edge safety
device), in addition in menu 4 a value unequal to
zero must be selected) (see figure 26)
Select menu 3 by pressing the PRG button. The flashing
figure displayed indicates the door's set open phase in
the OPEN position, which can be altered using the OPEN
or CLOSE buttons:
Display Waiting phase
0 * No automatic closing timer
1 10 sec.
2 20 sec.
3 30 sec.
4 45 sec.
5 60 sec.
6 90 sec.
7 120 sec.
8 150 sec.
9 180 sec.
When the automatic closing timer is active, the operator
lighting flashes two seconds before the start of travel. If
during this time the remote control is operated, the door's
set waiting phase in the OPEN position starts afresh.
If during two successive travel cycles the door encounters
an obstruction and reserves back to the OPEN travel
limit, then the door stays in this end-of-travel position and
an error message is issued.
Switch to menu 0 by pressing the PRG button.
5.2.2 Setting the photocell/closing edge safety device
(see figure 27)
Select menu 4 by pressing the PRG button. The flashing
figure displayed indicates the following settings which
can be altered using the OPEN or CLOSE button:
LS = photocell
SKS = closing edge safety device
Our photocells and closing edge safety devices incorpo-
rate a self-testing unit.
Terminals 71 18 19 18
Display query self-testing query self-testing
LS LS SKS SKS
0 * no no no no
1 yes no no no
2 yes yes no no
3 no no yes no
4 yes no yes no
5 yes yes yes no
6 no no yes yes
7 yes no yes yes
8 yes yes yes yes
Switch to menu 0 by pressing the PRG button.
5.2.3 Setting the function of the option relay (see figure 28)
Select menu 5 by pressing the PRG button. The flashing
figure displayed indicates the set function of the option
relay, which can be altered using the OPEN or CLOSE
buttons:
Display Function
0 * Operator:
no special function
Relay: OFF
Operator li
ghting:
continuous light while
the door is moving with programmed
afterglow phase
1 Operator:
2 sec. warning phase
Relay: slow-pulsing during the warning
phase and while the door is moving.
Operator li
ghting:
flashing rapidly during
the warning phase, continuous light while
the door is moving with programmed
afterglow phase
2 Operator:
2 sec. warning phase
Relay: permanently switched on during
the warning phase and while the door is
moving
Operator li
ghting: flashing rapidly during
the warning phase, continuous light while
the door is moving with programmed
afterglow phase
3 Operator:
no special function
Relay: picks up with operator lighting
Operator li
ghting: continuous light while
the door is moving with programmed
afterglow phase
4 as 1, but 5 sec. warning phase
5 as 2, but 5 sec. warning phase
6 Operator:
no special function
Relay: switched on permanently while
the door is moving (e.g. to switch lightning
relay with 100 % duty cycle)
Operator li
ghting: continuous light while
the door is moving with programmed
afterglow phase
For connection, see fig. 21.
Switch to menu 0 by pressing the PRG button.