Rev 1.01 2 900.0814
www.honeywellvideo.com
10/06
HVSsupport@honeywell.com
Figure 2. Standard Wiring
AWG
22
20
18
16
14
12
MAX. DISTANCE TO DOME
65 FEET (19 METERS)
100 FEET (30 METERS)
160 FEET (48 METERS)
260 FEET (79 METERS)
420 FEET (128 METERS)
650 FEET (198 METERS)
24 VAC POWER @1.1A
SPECIFICATIONS
WEIGHT : 5.5 lbs. (2.50 kg) WITH CAMERA
POWER REQUIREMENTS AT DOME: 24VAC, 50/60 Hz, 1.1A
NOTES:
1. TERMINAL STRIPS ACCEPT 18-22AWG WIRE
IF LARGER OR SMALLER WIRE IS REQUIRED, 18-22AWG MUST BE SPLICED
ONTO FIELD WIRE BEFORE INSERTING INTO TERMINAL STRIP.
2. ALL DIMENSIONS IN PARENTHESES ARE IN MILLIMETERS.
3. POWER SOURCE MUST BE SUFFICIENT ENOUGH TO MAINTAIN
A 21.6VAC INPUT AT DOME.
4. DATA CABLE SHIELD NOT CONNECTED AT DOME.
24Vac
Ground
24Vac
RX -
RX+
TX+
TX -
No Connection
TERMINAL STRIP TB1
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
Alarm 1
Common
Alarm 2
Common
Alarm 3
Common
Alarm 4
Common
TERMINAL STRIP TB2
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
ALIGNMENT TAB
CONTROL DATA
POWER
F1 1.6A 250V
LED POWER INDICATOR
REMOVABLE TOP PLATE
CABLE CLAMP
ALIGNMENT TAB
ALARM TERMINAL
STRIP
VIDEO BNC
CONNECTOR
J4
F1
Jumper W1
Jumper W2
Jumpers W3 & W4
Terminated Position 1 and 2 Last Dome on Data Loop
Unterminated Positions 2 and 3 All Intermediate Domes on Data Loop
Positions 2 and 3 All Domes
2-wire Positions 1 and 2 All Domes
Figure 3. Unshielded Twisted Pair (UTP) Option Wiring
SEE NOTES 1 & 2
SEE NOTES 1 & 2
ALIGNMENT TAB
W3
SW1
W4
TB3
W2
W1
TB1
ALIGNMENT TAB
TB2
SEE NOTE 2
BNC CONNECTOR
DATA OVER COAX (UTC) OPTION
VIDEO & DATA
SEE NOTE 2
CABLE CLAMP
0-90
90-180
180-270
270-365
365-455
0-300
300-600
600-900
900-1200
1200-1500
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
On
Off
Off
On
Off
On
Off
Off
Off
DIP Switch
Control & Video Over CAT5
SW1*
CAT5 Cable
Switch Position
Feet Meters 1 2 3 4
* Use lowest switch setting possible.
Ex: If cable run is 900 feet, use 600-900 switch setting.
Make sure only one switch is set to ON.
REMOVABLE TOP PLATE
Jumper W1
Jumper W2
Jumpers W3 & W4
Terminated Position 1 & 2 Last Dome on Data Loop
Unterminated Position 2 & 3 All Intermediate Domes on Data Lo op
Positions 2 & 3 All Domes
UTP Positions 1 & 2
Not Used Positions 2 & 3
SPECIFICATIONS
WEIGHT : 5.5 lbs. (2.5 kg) WITH CAMERA
POWER REQUIREMENTS AT DOME: 24VAC, 50/60 Hz, 1.1A
NOTES:
1.
IF LARGER OR SMALLER WIRE IS REQUIRED, AN APPROPRIATE AWG MUST BE SPLICED
ONTO FIELD WIRE BEFORE INSERTING INTO TERMINAL STRIP.
2.
3. ALL DIMENSIONS IN PARENTHESES ARE IN MILLIMETERS.
4. POWER SOURCE MUST BE 24VAC 10% AT POWER SUPPLY.
TERMINAL STRIPS TB1 & TB3 ACCEPT 18-22 AWG WIRE
TERMINAL STRIP TB2 ACCEPTS 12-18 AWG WIRE.
IF VIDEO IS ON UTP CABLE, BNC CONNECTOR IS NOT USED.
±
5. DATA CABLE SHIELD NOT CONNECTED AT DOME.
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
Alarm 1
Ground
Alarm 2
Gnd
RX-
RX+
TX+
TX-
TB3-1
TB3-2
Video +
Video -
TB2-1
TB2-2
TB2-3
24VAC
GND
24VAC
TERMINAL STRIP TB1 TERMINAL STRIP TB2
TERMINAL STRIP TB3
TWISTED PAIR
To use the board as standard (video over coax and 2-wire R 485):
Positions 1 & 2
Positions 2 & 3
S
Jumper W3
Jumper W4
AWG
22
20
18
16
14
12
MAX. DISTANCE TO DOME
65 FEET (19 METERS)
100 FEET (30 METERS)
160 FEET (48 METERS)
260 FEET (79 METERS)
420 FEET (128 METERS)
650 FEET (198 METERS)
24 VAC POWER @1.1A
2


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Honeywell HDT0D00x HD6 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Honeywell HDT0D00x HD6 in the language / languages: English, German, Dutch, French, Italian, Spanish as an attachment in your email.

The manual is 1,62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info